Features & Benefits

    Fully configurable fail-safe

    Setting of stroke position (extended, retracted or intermediate position) and delay feature for entering/leaving fail-safe mode for a reliable and optimal fail-safe function.

    Convenient, reliable setup

    Fully customisable by smartphone via Bluetooth using a TA-Dongle.

    Fully configurable

    More than 200 setup options allow input and output signals, binary input, relay, characteristics and many other parameters to be configured.

    Easy diagnostics

    Tracks the last 10 errors to allow system faults to be found quickly and health check of fail-safe function.

    Technical description

    Functions:

    Electronic fail-safe function
    Proportional control
    3-point control
    On-off control
    Manual override
    Stroke detection
    Mode, status and position indication
    Output signal VDC
    Stroke limitation setting
    Minimum stroke setting
    Valve blockage protection
    Valve clogging detection
    Error safe position
    Diagnostic/Logging
    Delayed start-up

    With relay board
    + 1 binary input, max. 100 Ω, cable max. 10 m or shielded.
    + 2 relays, max. 3A, 30 VDC/250 VAC on resistive load
    + Output signal in mA

    Fail-safe function:

    Programmable actuator’s stem extended, retracted or intermediate position on power failure.

    Supply voltage:

    24 VAC/VDC ±15%.
    100-240 VAC ±10%.
    Frequency 50/60 Hz ±3 Hz.

    Power consumption:

    Peak: < 18.4 VA (VAC); < 9.1 W (VDC)
    Operation: < 9 VA (VAC); < 4.8 W (VDC)
    Standby: < 1.6 VA (VAC); < 0.7 W (VDC)
    Peak consumption occurs for a short period after a power cut for recharging capacitors.

    Input signal:

    0(2)-10 VDC, Ri 47 kΩ.
    Adjustable sensitivity 0.1-0.5 VDC.
    0.33 Hz low pass filter.
    0(4)-20 mA Ri 500 Ω.
    Proportional:
    0-10, 10-0, 2-10 or 10-2 VDC
    0-20, 20-0, 4-20 or 20-4 mA
    Proportional split-range:
    0-5, 5-0, 5-10 or 10-5 VDC
    0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC
    2-6, 6-2, 6-10 or 10-6 VDC
    0-10, 10-0, 10-20 or 20-10 mA
    4-12, 12-4, 12-20 or 20-12 mA
    Proportional dual-range (for change-over):
    0-3.3 / 6.7-10 VDC,
    10-6.7 / 3.3-0 VDC,
    2-4.7 / 7.3-10 VDC or
    10-7.3 / 4.7-2 VDC.
    Default setting: Proportional 0-10 VDC.

    Output signal:

    0(2)-10 VDC, max. 8 mA, min. 1.25 kΩ.
    0(4)-20 mA, max. 700 Ω.
    Ranges: See “Input signal”.
    Default setting: Proportional 0-10 VDC.

    Characteristics:

    Linear, EQM 0.25 and inverted EQM 0.25.
    Default setting: Linear.

    Control speed:

    3, 4, 6, 8, 12 or 16 s/mm
    Default setting: 3 s/mm

    Fail-safe delay:

    Adjustable between 0 and 10 seconds.
    Default setting: 2 s

    Power supply stabilisation delay:

    Adjustable between 1 and 5 seconds.
    Default setting: 2 s

    Pre-charging time:

    < 60 s

    Adjusting force:

    750 N

    Temperature:

    Media temperature: 0°C – +120°C
    Operating environment: 0°C – +50°C (5-95%RH, non-condensing)
    Storage environment: -20°C – +50°C (5-95%RH, non-condensing)

    Ingress protection:

    IP54

    all directions

    (according to EN 60529)

    Protection class:

    (according to EN 61140)
    100-240 VAC: Class I
    24 VAC/VDC: Class I

    Stroke:

    22 mm

    Automatic detection of the valve lift (stroke detection).

    Noise level:

    Max. 40 dBA

    Weight:

    1,6 kg

    Connection to valve:

    By two M8 screws to the valve and by quick connection to the stem.

    Material:

    Cover: PBT
    Bracket: Alu EN44200

    Colour:

    Orange RAL 2011, grey RAL 7043.

    Marking:

    IMI TA, product name, article No. and technical specification.
    LED indication description.

    Certification CE:

    LV-D. 2014/35/EU: EN 60730-1, -2-14.
    EMC-D. 2014/30/EU: EN 60730-1, -2-14.
    RoHS-D. 2011/65/EU: EN 63000.

    Product standard:

    EN 60730

    (for Residential and industrial areas)

    Cable:

    Wire cross-section*: 0.5-2.0 mm2
    Protection class I: H05VV-F or similar
    Protection class III: LiYY or similar

    *) Note: Wire cross-sections must be chosen according to actuator power consumption and line length, such as the voltage supply to the actuator does not go below 20.4 VAC/VDC (24 VAC/VDC minus 15%).
    In case of VDC input signal on a 24 VAC/VDC powered actuator, the voltage drop on neutral line must be smaller than the defined hysteresis level for the VDC input signal.

    Articles

    TA-Slider 750 Fail-safe Plus

    Input signal: 0(2)-10 VDC, 0(4)-20 mA, 3-point, on-off

    With binary input, relays, mA output signal

    Supply voltage
    EAN
    Article No
    24 VAC/VDC
    5902276898822
    322226-10319
    100-240 VAC
    5902276898839
    322226-40319
    Additional equipment

    For Bluetooth communication with the HyTune app, transfer configuration settings and manual override.

    TA-Dongle

    For Bluetooth communication with the HyTune app, transfer configuration settings and manual override.

    EAN
    Article No
    5901688828632
    322228-00001
    Accessories

    Including spindle top (extension) and extended screws.Temperature range till -10 °C.Voltage 24 VAC ±10% 50/60 Hz ±5%.Power PN approx. 30 W.Current 1,4 A.Surface temperature max. 50 °C.

    Stem heater

    Including spindle top (extension) and extended screws.
    Temperature range till -10 °C.
    Voltage 24 VAC ±10% 50/60 Hz ±5%.
    Power PN approx. 30 W.
    Current 1,4 A.
    Surface temperature max. 50 °C.

    For valve
    DN
    L
    H
    W
    D
    EAN
    Article No
    146
    49
    70
    30
    TA-Modulator
    40-50
    5902276819483
    322042-80802
    TA-Modulator
    65-200
    3831112534834
    322042-80010
    KTM 512
    15-50
    3831112533431
    322042-80900
    KTM 512
    65-125
    3831112533455
    322042-81401

    TA-Slider_750_Fail-safe_Plus

    Select a format Download

    Drawings