Features & Benefits

    Adjustable maximum flow

    Adjustable Cvmax technology allows setting to design flow.

    Independent, inherent EQM characteristic

    Proper EQM valve characteristic and high authority for all settings.

    Self-sealing measuring points

    Simple and accurate measurement for balancing, trouble shooting and power measurement.

    Technical description

    Application:

    Heating and cooling systems.

    Functions:

    Control (EQM)
    Differential pressure control
    Pre-setting (max. flow)
    Measuring (ΔH, T, q)
    Shut-off (for isolation during system maintenance)
    Flushing (of the system)

    Dimension:

    Size 1 1/4" - 2"
    (Size 2 1/2" - 6": See TA-Modulator)

    Pressure class:

    232 psi

    Differential pressure (ΔpV):

    Max. differential pressure (ΔpVmax):
    116 psi
    Min. differential pressure (ΔpVmin):
    2.18 psi
    (Valid for position 10, fully open. Other positions will require lower differential pressure, check with the software HySelect.)

    ΔpVmax = The maximum allowed pressure drop over the valve to fulfill all stated performances.

    ΔpVmin = The minimum recommended pressure drop over the valve, for proper differential pressure control.

    Recommended flow range:

    The flow (qmax) can be set within the range [gpm]:

    1 1/4": 3.87 - 18.54
    1 1/2": 4.45 - 27.3
    2": 11.93 - 48.9

    qmax = gpm at each setting and fully open valve plug.

    Lift:

    0.787 in

    Rangeability:

    >100 (for all recommended settings)

    Leakage rate:

    Tight sealing

    Characteristics:

    Independent EQM.

    Temperature:

    Max. working temperature: 248 °F
    Min. working temperature: -4 °F

    Media:

    Water or neutral fluids, water-glycol mixtures (0-57%).

    (For other media contact your local sales office.)

    Material:

    Valve body: AMETAL®
    Valve plug: AMETAL®
    Seat seal: EPDM/Stainless steel
    Spindle seal: EPDM O-ring
    O-rings: EPDM
    Valve insert: AMETAL®/PPS/PTFE
    Δp insert: Stainless steel/PPS
    Membrane: HNBR
    Springs: Stainless steel
    Spindle: Stainless steel


    AMETAL® is the dezincification resistant alloy of IMI Hydronic Engineering.

    Surface treatment:

    Non treated

    Marking:

    TAH, IMI, size (DN/inch), PN, DR, serial No and flow direction arrow.

    Size 6": CE 0062 *

    *) Notified body.

    Connection:

    Pipe threads NPT according to ANSI/ASME B1.20.1-1983. Complete thread according to ANSI B16.15-1985.

    Actuators:

    TA-Slider 750
    TA-MC100 FSE/FSR (fail-safe)
    For more details on actuators, see separate technical leaflets.

    Articles

    Female thread

    Pipe threads NPT according to ANSI/ASME B1.20.1-1983. Complete thread according to ANSI B16.15-1985.

    Size
    d
    D [in]
    D1 [in]
    L1 [in]
    H1* [in]
    qmax
    [gpm]
    Weight
    [lb]
    Article No **
    North America
    Article No
    International
    232 psi
    1 1/4"
    1 1/4 NPT
    5.11
    5.04
    10.75
    7.32
    18.54
    15.4
    22202-003032
    22202-002032
    1 1/2"
    1 1/2 NPT
    5.11
    5.04
    10.94
    7.32
    27.3
    15.6
    22202-003040
    22202-002040
    2"
    2 NPT
    5.11
    5.04
    11.34
    7.48
    48.9
    18.5
    22202-003050
    22202-002050

    → = Flow direction


    **) Distributed by Victaulic.

    Articles – Actuators

    TA-Slider 750, TA-MC100FSE/FSR

    Sizes 6": Adapter for actuator to be ordered separately.

    For more variants and details on actuators, see separate technical leaflets or contact IMI Hydronic Engineering.

    Type
    Supply voltage
    Valve size
    EAN
    Article No
    TA-Slider 750
    24 VAC/VDC
    1 1/4" - 6"
    5901688828458
    322226-10110
    TA-Slider 750
    100-240 VAC
    1 1/4" - 6"
    5902276883620
    322226-40110
    TA-MC100FSE
    24 VAC
    1 1/4" - 6"
    3831112512122
    61-100-101
    TA-MC100FSR
    24 VAC
    1 1/4" - 6"
    3831112512146
    61-100-201
    Adapters for actuators
    Accessories

    Suitable when insulation is used.Stainless steel/EPDM/Brass.

    Venting extension

    Suitable when insulation is used.
    Stainless steel/EPDM/Brass.

    d
    D [in]
    L [in]
    EAN
    Article No
    M6
    0.47
    2.76
    3831112531727
    52 759-220

    Can be installed without draining of the system.AMETAL®/Stainless steel/EPDM

    Measuring point, extension 2.36 in.

    Can be installed without draining of the system.
    AMETAL®/Stainless steel/EPDM

    L [in]
    EAN
    Article No
    2.36
    7318792812804
    52 179-006

    22202002040

    Select a format Download

    TA-FUSION-P_NPT_TA-Slider

    Select a format Download

    TA-FUSION-P_NPT_TA-Slider_persp

    Select a format Download

    TA-FUSION-P_NPT_TA-Slider_left_persp

    Select a format Download

    22202002050

    Select a format Download

    22202002032

    Select a format Download

    TA-FUSION-P_NPT_TA-Slider_left

    Select a format Download