Features & Benefits
User-friendly design
Ergonomic and custom designed user-interface ensures easy and more comfortable balancing.
Interactive software
Step by step software wizards for measuring, balancing and trouble shooting ensure a fast commissioning process.
Wireless communication
For reliable balancing, a fully charged TA-SCOPE provides three days of power-efficient wireless performance.
DpS-Visio
The Dp Sensor has an OLED display for showing Dp measurement, temperature and status. It also has an automatic flushing and calibration function.
Technical Information
Functions:
TA-SCOPE is a balancing instrument for measuring and documenting of differential pressure (Δp), flow, temperature and power in hydronic systems.
TA-SCOPE consists of two main components:
Handheld unit – computer-based unit programmed with the TA valve characteristics. Straightforward functions with easy-to-follow instructions on the colour display.
Differential Pressure Sensor unit – the DpS-Visio communicates wirelessly with the Handheld and has an OLED display for showing its status, measured data and other information.
TA-SCOPE automatically performs calibration when needed. The design of the sensor unit and a short flow-through during calibration eliminate measurement errors caused by insufficient venting of the measuring device.
Measurement range:
Total pressure:
TA-SCOPE max. 232 psi
TA-SCOPE HP max. 362 psi
Differential pressure:
TA-SCOPE 0 - 72.5 psi
TA-SCOPE HP 0 - 145 psi
Recommended pressure range during flow measurements:
TA-SCOPE 0.02 - 72.5 psi
TA-SCOPE HP 0.5 - 145 psi
Measurement deviation:
Differential pressure:
TA-SCOPE 0.015 psi or 1% of reading, whichever is the highest
TA-SCOPE HP 0.029 psi or 1% of reading, whichever is the highest
Flow: as for differential pressure + valve deviation
Temperature: <0.36°F
Temperature:
Temperature liquid medium measurement: -4°F – +248°F
Ambient temperature for the instrument:
During operation and charging: +32°F – +104°F
During storage*: -4°F – +150°F
*) Do not leave water in the sensor when there is a risk of freezing.
Humidity:
Ambient humidity: max. 90%RH
Battery capacity, operating and charge times:
Handheld unit:
- battery capacity: 4 400 mAh
- operating time (with backlight on): >25 h
- charge time to full capacity: 6-7 h
DpS-Visio (Dp sensor unit):
- battery capacity: 1 400 mAh
- operating time (continuous measurements): >25 h
- charge time to full capacity: 2.5 h
Logging time (in sleep mode): >100 days
Ingress protection:
Handheld unit (in wireless mode): IP64
Dp sensor unit (in wireless mode): IP64
Safety pressure and temperature probe: IP65
Digital temperature sensor: IP65
Charger:
Input voltage: 100-240 VAC
Input frequency: 50-60 Hz
Connectors: EU, UK, US, AU/NZ
Case dimensions:
TA-SCOPE Premium case:
LxWxH = 16.8x11.4x6.3 in
TA-SCOPE case:
LxWxH = 13.2x11.4x5.9 in
Articles
TA-SCOPE HP Premium
Case dimension: LxWxH = 16.8x11.4x6.3 in
Version* | EAN | Article No | |
INT | International version | 7318793986900 | 52 199-102 |
LAM | Latin America | 7318793988904 | 52 199-118 |
US | USA | 7318793988508 | 52 199-114 |
*) Version = Market related product range. All instrument versions include all of the above languages.
Quick Guide included. User manuals available on USB stick.
TA-SCOPE Premium
Case dimension: LxWxH = 16.8x11.4x6.3 in
Version* | EAN | Article No | |
INT | International version | 7318793982506 | 52 199-002 |
LAM | Latin America | 7318793986405 | 52 199-018 |
US | USA | 7318793984906 | 52 199-014 |
*) Version = Market related product range. All instrument versions include all of the above languages.
Quick Guide included. User manuals available on USB stick.
TA-SCOPE HP
Case dimension: LxWxH = 13.2x11.4x5.9 in
Version* | EAN | Article No | |
INT | International version | 7318794007406 | 52 199-302 |
LAM | Latin America | 7318794011106 | 52 199-318 |
US | USA | 7318794010703 | 52 199-314 |
*) Version = Market related product range. All instrument versions include all of the above languages.
Quick Guide included. User manual available for download on www.imi-hydronic.com.
TA-SCOPE
Case dimension: LxWxH = 13.2x11.4x5.9 in
Version* | EAN | Article No | |
INT | International version | 7318794006409 | 52 199-202 |
LAM | Latin America | 7318794009301 | 52 199-218 |
US | USA | 7318794008908 | 52 199-214 |
*) Version = Market related product range. All instrument versions include all of the above languages.
Quick Guide included. User manual available for download on www.imi-hydronic.com.
For use with SPP and SPTP
Measuring hose
For use with SPP and SPTP
Length [in] | EAN | Article No | |
20 | Red | 7318793998507 | 52 199-953 |
20 | Blue | 7318793998606 | 52 199-954 |
Measuring hose with twin needle
Length [in] | EAN | Article No |
6 | 7318793985903 | 52 199-999 |
To keep SPTP cable and hose together
Cable wrapping
To keep SPTP cable and hose together
EAN | Article No |
7640161635791 | 310 355-01 |
Digital temperature sensor (DTS)
EAN | Article No |
7318793983503 | 52 199-941 |
The handheld unit (Hh) can communicate with several Dp sensor units (DpS-Visio). Establish communication by connecting the cable (included in the TA-SCOPE case) between the handheld unit and the Dp sensor unit.Included: 2 measuring hoses 500 mm, 2 identification rings, 2 safety pressure probes (SPP) and 1 charging cable.
Dp sensor unit (DpS-Visio)
The handheld unit (Hh) can communicate with several Dp sensor units (DpS-Visio). Establish communication by connecting the cable (included in the TA-SCOPE case) between the handheld unit and the Dp sensor unit.
Included: 2 measuring hoses 500 mm, 2 identification rings, 2 safety pressure probes (SPP) and 1 charging cable.
Version | EAN | Article No | |
Standard | 0-72.5 psi | 7318794034204 | 52 199-971 |
HP (high pressure) | 0-145 psi | 7318794034303 | 52 199-972 |
Safety pressure and temperature probe (SPTP)
For use with measuring hoses 52 199-953/-954 and extended hoses 52 199-997/-998.
EAN | Article No |
7318793998408 | 52 199-952 |
Safety pressure probe (SPP)
For use with measuring hoses 52 199-953/-954 and extended hoses 52 199-997/-998.
EAN | Article No |
7318793998309 | 52 199-951 |
With shut-off valve
Measuring hose
With shut-off valve
Length | EAN | Article No | |
20 in. | Red | 7318793985507 | 52 199-995 |
20 in | Blue | 7318793985606 | 52 199-996 |
9.8 ft. | Red | 7318793985705 | 52 199-997 |
9.8 ft. | Blue | 7318793985804 | 52 199-998 |
"DpS 1" and "DpS 2" for marking the DpS-Visio when using TA-Wireless. To be placed on measuring hoses.
Identification rings
"DpS 1" and "DpS 2" for marking the DpS-Visio when using TA-Wireless.
To be placed on measuring hoses.
EAN | Article No | |
DpS 1 | 7640161635807 | 310 399-01 |
DpS 2 | 7640161635814 | 310 399-02 |
Extension cable for digital temperatur sensor
Length [ft] | EAN | Article No |
16.4 | 7318793985408 | 52 199-994 |
Measuring needle, angle
EAN | Article No |
7318793787507 | 307 635-62 |
With 4 USB plugs.Excl. charging cables.
Multi-charger
With 4 USB plugs.
Excl. charging cables.
EAN | Article No | |
EU, UK, US, AU/NZ | 311 100-01 |
For older valves and TA-BVS
Chucks
For older valves and TA-BVS
EAN | Article No | |
Red | 7318793786609 | 309 748-60 |
Blue | 7318793786708 | 309 748-61 |
To connect or charging different devices.
Cables
To connect or charging different devices.
EAN | Article No | ||
Cable A | |||
Handheld - Multi-charger | 310 397-02 | ||
Cable B | |||
Handheld - DpS-Visio / PC - DpS-Visio / DpS-Visio - Multi-charger | 7318794045101 | 310 278-02 | |
Cable C | |||
Handheld - PC / Handheld - DpS (up to 08.2017) | 7318793996305 | 310 278-01 |
Thread connections G1/2 and G3/4
Measuring nipple
Thread connections G1/2 and G3/4
EAN | Article No | |
G1/2 | 7318793536808 | 52 197-303 |
G3/4 | 7318793536907 | 52 197-304 |
Can be installed without draining of the system.AMETAL®/Stainless steel/EPDM
Measuring point, extension 2.36 in.
Can be installed without draining of the system.
AMETAL®/Stainless steel/EPDM
L [in] | EAN | Article No |
2.36 | 7318792812804 | 52 179-006 |
Hose and needle can’t be disconnected.
Measuring hose with measuring needle, angle
Hose and needle can’t be disconnected.
Length | EAN | Article No | |
20 in. | Red | 7318794044906 | 311 074-61 |
20 in. | Blue | 7318794045002 | 311 074-60 |
Spare part to measuring hoses
Filter
Spare part to measuring hoses
EAN | Article No | ||
→ 09.2018 | 1 pc | 7318793741301 | 309 206-01 |
10.2018 → | 4 pcs | 7318794044807 | 311 062-62 |