Features & Benefits
Make-up water limitation
Automatic limitation of make-up water with the help of the PNEUMATEX BrainCube control unit.
BrainCube control
Self-optimising with memory function (PI, PI 6, PI 9).
Technical Information
Application:
Heating, solar and chilled water systems.
For systems according to EN 12828, EN 12976, ENV 12977, EN 12952, EN 12953.
Media:
Entry: potable water
Outflow(Consumer side): Non-aggressive and non-toxic system media.
Addition of antifreeze agent up to 50%.
Pressure:
Min. admissible pressure, PSmin: 0 bar
Max. admissible pressure, PS: see Articles
Temperature:
Max. admissible temperature, TS: 65 °C (PX, PIX), 30 °C (PI9, PI9F)
Min. admissible temperature, TSmin: 0 °C
Max. admissible ambient temperature, TA: 40 °C
Supply voltage:
1 x 230 V (± 10 %) / 50 Hz
Electrical connections:
Pleno PIX, PI9(F):
Onsite fuses according to power demand and local norms
4 potential free outputs (NO) for external alarm indication (230V max. 2A)
1 RS 485 In/Output
1 Ethernet RJ45 plug socket
1 USB Hub plug socket
Enclosure class:
Pleno PX: IP 65
Pleno PIX: IP 54
Pleno PI9(F): IP 54
Material:
Metal components with medium contact:
carbon steel, cast iron, stainless steel,
brass, and gunmetal.
Standard:
Pleno PIX, PI9(F):
Constructed according to
LV-D. 2014/35/EU
EMC-D. 2014/30/EU
Pleno P BA4 R: EN1717 (protection class 4)
Articles
Hydraulic unit for water make-up operation with Compresso Connect. Water make-up without pumps. 1 solenoid valve, 1 electronic water meter, connection for Pleno P BA4 R.Connection in (Swm): G3/4.Connection out (Sout): G1/2.
Pleno PX
Hydraulic unit for water make-up operation with Compresso Connect. Water make-up without pumps. 1 solenoid valve, 1 electronic water meter, connection for Pleno P BA4 R.
Connection in (Swm): G3/4.
Connection out (Sout): G1/2.

Type | PS [bar] | B | H | T | m [kg] | Pel [kW] | Kvs | EAN | Article No |
PX | 10 | 198 | 356 | 150 | 1,5 | 0,02 | 1,4 | 7640161641792 | 301060-10011 |
T = Depth of the device
Pel = Electric load
Control unit TecBox. Water make-up without pumps. 1 solenoid valve, 1 electronic water meter, connection for Pleno P BA4 R, BrainCube control.Connection in (Swm): G3/4.Connection out (Sout): G1/2.
Pleno PIX Connect
Control unit TecBox. Water make-up without pumps. 1 solenoid valve, 1 electronic water meter, connection for Pleno P BA4 R, BrainCube control.
Connection in (Swm): G3/4.
Connection out (Sout): G1/2.

Type | PS [bar] | B | H | T | m [kg] | Pel [kW] | Kvs | EAN | Article No |
PIX | 10 | 198 | 392 | 190 | 4,3 | 0,04 | 1,4 | 5901688829851 | 301060-20001 |
T = Depth of the device
Pel = Electric load
Hydraulic unit for water make-up operation with Vento/Transfero Connect, Pleno PX/PIX, Simply Compresso C 2.1-80 SWM, and in combination with Pleno Refill modules. Features a shut off valve, check valve, filter and a type BA backflow preventer (protection class 4) according to EN 1717.Connection (Swm): G1/2
Pleno P BA4 R
Hydraulic unit for water make-up operation with Vento/Transfero Connect, Pleno PX/PIX, Simply Compresso C 2.1-80 SWM, and in combination with Pleno Refill modules. Features a shut off valve, check valve, filter and a type BA backflow preventer (protection class 4) according to EN 1717.
Connection (Swm): G1/2

Type | PS [bar] | B | L | H | m [kg] | qwm [l/h] | EAN | Article No |
BA4 R | 10 | 210 | 1300 | 135 | 1,1 | 350* 250** 50*** q(pw-pout) **** | 7640161630147 | 813 3310 |
qwm = make-up water flow
* maximum average value for make-up water degassing with Vento V/VI and Transfero TV/TVI
** maximum average value for make-up water degassing with Vento Compact
*** when using flow limiter for operation with low flow water treatment cartridges
**** for combination with Pleno PX/PIX see q(pw-pout) diagram in Pleno Connect datasheet
T = Depth of the device
Control unit TecBox. Water make-up with pumps.1 pump, 1 electronic water meter, integrated wall mounting bracket. Integrated break tank type AB5.Connection in (Swm): G1/2Connection out (Sout): G3/4
Pleno PI 9.1 F Connect
Control unit TecBox. Water make-up with pumps.
1 pump, 1 electronic water meter, integrated wall mounting bracket.
Integrated break tank type AB5.
Connection in (Swm): G1/2
Connection out (Sout): G3/4

Type | PS [bar] | B | H | T | m [kg] | Pel [kW] | SPL [dB(A)] | dpu [bar] | qwm [l/h] | EAN | Article No |
PI 9.1 F | 10 | 520 | 500 | 350 | 24 | 0,75 | 74 | 1-8 | 100-450 *) | 5901688829868 | 301060-50002 |
T = Depth of the device
Pel = Electric load
dpu = Working pressure range
qwm = Water make-up flow
*) depending on pressure values at Swm and Sout
Control unit TecBox. Water make-up with pumps.2 pumps (one for reserve), 1 electronic water meter. Floor standing.Integrated break tank type AB5.Connection in (Swm): G1/2Connection out (Sout): G3/4
Pleno PI 9.2 Connect
Control unit TecBox. Water make-up with pumps.
2 pumps (one for reserve), 1 electronic water meter. Floor standing.
Integrated break tank type AB5.
Connection in (Swm): G1/2
Connection out (Sout): G3/4

Type | PS [bar] | B | H | T | m [kg] | Pel [kW] | SPL [dB(A)] | dpu [bar] | qwm [l/h] | EAN | Article No |
PI 9.2 | 10 | 520 | 1056 | 350 | 33 | 0,75 | 74 | 1-8 | 100-450 *) | 5901688829882 | 301060-40002 |
T = Depth of the device
Pel = Electric load
dpu = Working pressure range
qwm = Water make-up flow
*) depending on pressure values at Swm and Sout
Control unit TecBox. Water make-up with pumps.1 pump, 1 electronic water meter. Floor standing.Integrated break tank type AB5.Connection in (Swm): G1/2Connection out (Sout): G3/4
Pleno PI 9.1 Connect
Control unit TecBox. Water make-up with pumps.
1 pump, 1 electronic water meter. Floor standing.
Integrated break tank type AB5.
Connection in (Swm): G1/2
Connection out (Sout): G3/4

Type | PS [bar] | B | H | T | m [kg] | Pel [kW] | SPL [dB(A)] | dpu [bar] | qwm [l/h] | EAN | Article No |
PI 9.1 | 10 | 520 | 1056 | 350 | 25 | 0,75 | 74 | 1-8 | 100-450 *) | 5901688829875 | 301060-30003 |
T = Depth of the device
Pel = Electric load
dpu = Working pressure range
qwm = Water make-up flow
*) depending on pressure values at Swm and Sout
3/4” swivelling nut, 3/4” external thread suitable for flat gasket, with flow limiter. In compliance with SWKI-BT-102-1.
Demineralisation unit with wall mounting bracket and 25 µm filter
3/4” swivelling nut, 3/4” external thread suitable for flat gasket, with flow limiter. In compliance with SWKI-BT-102-1.


Type | Capacity l x °dH | Sin | Sout | H | L1 | L2 | m [kg] | EAN | Article No |
Refill Demin 2000 filter | 2000 | G3/4 | G3/4 | 571 | 366 | 271 | 4,1 | 813 3015 | |
Refill Demin 4000 filter | 4000 | G3/4 | G3/4 | 571 | 513 | 420 | 7,8 | 813 3016 |
→ = Flow direction
3/4” swivelling nut, 3/4” external thread suitable for flat gasket, with flow limiter.
Softening unit with wall mounting bracket and 25 µm filter
3/4” swivelling nut, 3/4” external thread suitable for flat gasket, with flow limiter.


Type | Capacity l x °dH | Sin | Sout | H | L1 | L2 | m [kg] | EAN | Article No |
Refill 6000 filter | 6000 | G3/4 | G3/4 | 644 | 366 | 271 | 4,1 | 7640153570864 | 813 3010 |
Refill 12000 filter | 12000 | G3/4 | G3/4 | 644 | 513 | 420 | 7,8 | 7640161631946 | 813 3011 |
→ = Flow direction
Demineralisation unit
3/4" swivelling nut, 3/4" external thread suitable for flat gasket.
Nominal pressure: PS 8
Max. working temperature: 45°C
Min. working temperature: > 4°C

Type | Capacity l x °dH | Sin | Sout | D | H | L | m [kg] | EAN | Article No |
Refill Demin 13500 | 13500 | G3/4 | G3/4 | 220 | 466 | 455 | 13 | 7640161630505 | 813 3260 |
Refill Demin 18000 | 18000 | G3/4 | G3/4 | 270 | 458 | 455 | 16,2 | 7640161630512 | 813 3270 |
→ = Flow direction
Softening unit
3/4" swivelling nut, 3/4" external thread suitable for flat gasket.
Nominal pressure: PS 8
Max. working temperature: 45°C
Min. working temperature: > 4°C

Type | Capacity l x °dH | Sin | Sout | D | H | L | m [kg] | EAN | Article No |
Refill 16000 | 16000 | G3/4 | G3/4 | 195 | 383 | 455 | 9,1 | 7640161630475 | 813 3210 |
Refill 36000 | 36000 | G3/4 | G3/4 | 220 | 466 | 455 | 13 | 7640161630482 | 813 3220 |
Refill 48000 | 48000 | G3/4 | G3/4 | 270 | 458 | 455 | 16,2 | 7640161630499 | 813 3230 |
→ = Flow direction
Images

30106050002
Select a format Download
30106030003
Select a format Download
Pleno_Connect_cover
Select a format Download
30106020001
Select a format Download
30106040002
Select a format Download
30106050002_front
Select a format Download
30106040002_front
Select a format Download
Pleno_P_8133310
Select a format Download
Pleno_PX
Select a format Download