Features & Benefits

    2 in 1

    The only pressurisation unit with integrated cyclonic vacuum degassing

    Higher Efficiency Cyclonic vacuum degassing

    At least 50% higher efficiency than most other vacuum degassing systems.

    Easy Commissioning, Remote Access and Trouble-shooting

    Automatic calibration and integrated standard connections to our IMI Webserver and to BMS.

    Technical description – Control unit TecBox

    Applications:

    Heating, solar and chilled water systems.
    For systems according to EN 12828, SWKI HE301-01, solar systems according to EN 12976, ENV 12977, with on-site excess temperature protection in case of power outage.

    Media:

    Non-aggressive and non-toxic system media.
    Ethylene or propylene glycol-based antifreeze up to 50%.

    Pressure:

    Min. admissible pressure, PSmin: -1 bar
    Max. admissible pressure, PS: see Articles

    Temperature:

    Max. admissible temperature, TS: 90°C
    Min. admissible temperature, TSmin: 0°C

    Max. admissible ambient temperature, TA: 40°C
    Min. admissible ambient temperature, TAmin: 5°C

    Accuracy:

    Precision pressure maintenance ±0,2 bar.

    Supply voltage:

    1 x 230 V (-/+ 10 %), 50 Hz

    Electrical connections:

    1 plug socket (incl. counter plug) for supply voltage 230V (external fuses according power needs and local electrical norms)
    4 potential free outputs (NO) for external alarm indication (230V max. 2A)
    1 RS 485 In/Output
    1 Ethernet RJ45 plug socket
    1 USB Hub plug socket

    Enclosure class:

    IP54 according to EN 60529

    Mechanical connections:

    Sin1/Sin2: inlet from the system G3/4"
    Sout: outlet to the system G3/4"
    Swm: inlet water make-up G3/4"
    Sv: connection of the vessel G1 1/4"

    Material:

    Metal components with medium contact: carbon steel, cast iron, stainless steel, AMETAL®, brass, gunmetal.

    Transportation and storage:

    In frostless, dry places.

    Standard:

    Constructed according to

    MD 2006/42/EC, Annex II 1.A
    EMC-D. 2014/30/EU

    Technical description – Expansion vessels

    Applications:

    Only together with TecBox Control Unit.
    See Applications under Technical description - TecBox Control Unit.

    Media:

    Non-aggressive and non-toxic system media.
    Ethylene or propylene glycol-based antifreeze up to 50%.

    Pressure:

    Min. admissible pressure, PSmin: 0 bar
    Max. admissible pressure, PS: 2 bar

    Temperature:

    Max. admissible bag temperature, tB: 70°C
    Min. admissible bag temperature, tBmin: 5°C

    For PED purposes:
    Max. admissible temperature, tsmax: 120°C
    Min. admissible temperature, tsmin: -10°C

    Material:

    Steel. Color beryllium.
    Airproof butyl bag according to EN 13831.

    Transportation and storage:

    In frostless, dry places.

    Standard:

    Constructed according to PED 2014/68/EU.

    Warranty:

    Transfero TU, TU...E: 5-year warranty for the vessel.
    Transfero TG, TG...E: 5-year warranty for the airproof butyl bag.

    Control unit TecBox, Transfero TV Connect Heating

    Precision pressure maintenance ±0,2 bar. 1 pump. 1 spill valve and two motor driven valves for degassing and pressurisation.

    Transfero TV .1 E Connect

    Precision pressure maintenance ±0,2 bar. 1 pump. 1 spill valve and two motor driven valves for degassing and pressurisation.

    1 solenoid valve and 1 water meter for water make-up.

    Type
    W
    H
    T
    m
    [kg]
    Pel
    [kW]
    dpu
    [bar]
    SPL
    [dB(A)]
    EAN
    Article No
    10 bar (PS)
    TV 4.1 E
    500
    920
    530
    42
    0,75
    1-2,5
    ~55*
    7640161629462
    811 1500
    TV 6.1 E
    500
    920
    530
    44
    1,1
    1,5-3,5
    ~55*
    7640161629479
    811 1501
    TV 8.1 E
    500
    920
    530
    45
    1,4
    2-4,5
    ~55*
    7640161629486
    811 1502
    TV 10.1 E
    500
    1300
    530
    50
    1,7
    3,5-6,5
    ~60*
    7640161629493
    811 1503
    13 bar (PS)
    TV 14.1 E
    500
    1300
    530
    69
    1,7
    5,5-10
    ~60*
    7640161629509
    811 1504

    T = Depth of the device

    dpu = Working pressure range

    *) Pump operation

    Precision pressure maintenance ±0,2 bar. 2 pumps. 1 spill valve for degassing and pressurisation. 1 spill valve for peak load pressurisation.

    Transfero TV .2 EH Connect

    Precision pressure maintenance ±0,2 bar. 2 pumps. 1 spill valve for degassing and pressurisation. 1 spill valve for peak load pressurisation.

    1 solenoid valve and 1 water meter for water make-up.

    Type
    W
    H
    T
    m
    [kg]
    Pel
    [kW]
    dpu
    [bar]
    SPL
    [dB(A)]
    EAN
    Article No
    10 bar (PS)
    TV 4.2 EH
    680
    920
    530
    54
    1,5
    1-2,5
    ~55*
    7640161629554
    811 1520
    TV 6.2 EH
    680
    920
    530
    57
    2,2
    1,5-3,5
    ~55*
    7640161629561
    811 1521
    TV 8.2 EH
    680
    920
    530
    60
    2,8
    2-4,5
    ~55*
    7640161629578
    811 1522
    TV 10.2 EH
    680
    1300
    530
    70
    3,4
    3,5-6,5
    ~60*
    7640161629585
    811 1523
    13 bar (PS)
    TV 14.2 EH
    680
    1300
    530
    97
    3,4
    5,5-10
    ~60*
    7640161629592
    811 1524

    T = Depth of the device

    dpu = Working pressure range

    *) Pump operation

    Precision pressure maintenance ±0,2 bar. 1 pump. 1 spill valve for degassing and pressurisation. 1 spill valve for peak load pressurisation.

    Transfero TV .1 EH Connect

    Precision pressure maintenance ±0,2 bar. 1 pump. 1 spill valve for degassing and pressurisation. 1 spill valve for peak load pressurisation.

    1 solenoid valve and 1 water meter for water make-up.

    Type
    W
    H
    T
    m
    [kg]
    Pel
    [kW]
    dpu
    [bar]
    SPL
    [dB(A)]
    EAN
    Article No
    10 bar (PS)
    TV 4.1 EH
    500
    920
    530
    43
    0,75
    1-2,5
    ~55*
    7640161629516
    811 1510
    TV 6.1 EH
    500
    920
    530
    46
    1,1
    1,5-3,5
    ~55*
    7640161629523
    811 1511
    TV 8.1 EH
    500
    920
    530
    47
    1,4
    2-4,5
    ~55*
    7640161629530
    811 1512
    TV 10.1 EH
    500
    1300
    530
    52
    1,7
    3,5-6,5
    ~60*
    7640161629547
    811 1513
    13 bar (PS)
    TV 14.1 EH
    500
    1300
    530
    72
    1,7
    5,5-10
    ~60*
    7640161629851
    811 1514

    T = Depth of the device

    dpu = Working pressure range

    *) Pump operation

    Control unit TecBox, Transfero TV Connect Cooling

    Precision pressure maintenance ±0,2 bar. 1 pump. 1 spill valve for degassing and pressurisation. 1 spill valve for peak load pressurisation.

    Transfero TV .1 EHC Connect

    Precision pressure maintenance ±0,2 bar. 1 pump. 1 spill valve for degassing and pressurisation. 1 spill valve for peak load pressurisation.

    1 solenoid valve and 1 water meter for water make-up.

    Cooling insulation with condensation water protection.

    Type
    W
    H
    T
    m
    [kg]
    Pel
    [kW]
    dpu
    [bar]
    SPL
    [dB(A)]
    EAN
    Article No
    10 bar (PS)
    TV 4.1 EHC
    500
    920
    530
    44
    0,75
    1-2,5
    ~55*
    7640161629653
    811 1540
    TV 6.1 EHC
    500
    920
    530
    47
    1,1
    1,5-3,5
    ~55*
    7640161629660
    811 1541
    TV 8.1 EHC
    500
    920
    530
    48
    1,4
    2-4,5
    ~55*
    7640161629677
    811 1542
    TV 10.1 EHC
    500
    1300
    530
    51
    1,7
    3,5-6,5
    ~60*
    7640161629684
    811 1543
    13 bar (PS)
    TV 14.1 EHC
    500
    1300
    530
    73
    1,7
    5,5-10
    ~60*
    7640161629868
    811 1544

    T = Depth of the device

    dpu = Working pressure range

    *) Pump operation

    Precision pressure maintenance ±0,2 bar. 1 pump. 1 spill valve and two motor driven valves for degassing and pressurisation.

    Transfero TV .1 EC Connect

    Precision pressure maintenance ±0,2 bar. 1 pump. 1 spill valve and two motor driven valves for degassing and pressurisation.

    1 solenoid valve and 1 water meter for water make-up.

    Cooling insulation with condensation water protection.

    Type
    W
    H
    T
    m
    [kg]
    Pel
    [kW]
    dpu
    [bar]
    SPL
    [dB(A)]
    EAN
    Article No
    10 bar (PS)
    TV 4.1 EC
    500
    920
    530
    43
    0,75
    1-2,5
    ~55*
    7640161629608
    811 1530
    TV 6.1 EC
    500
    920
    530
    45
    1,1
    1,5-3,5
    ~55*
    7640161629615
    811 1531
    TV 8.1 EC
    500
    920
    530
    46
    1,4
    2-4,5
    ~55*
    7640161629622
    811 1532
    TV 10.1 EC
    500
    1300
    530
    51
    1,7
    3,5-6,5
    ~60*
    7640161629639
    811 1533
    13 bar (PS)
    TV 14.1 EC
    500
    1300
    530
    70
    1,7
    5,5-10
    ~60*
    7640161629646
    811 1534

    T = Depth of the device

    dpu = Working pressure range

    *) Pump operation

    Precision pressure maintenance ±0,2 bar. 2 pumps. 1 spill valve for degassing and pressurisation. 1 spill valve for peak load pressurisation.

    Transfero TV .2 EHC Connect

    Precision pressure maintenance ±0,2 bar. 2 pumps. 1 spill valve for degassing and pressurisation. 1 spill valve for peak load pressurisation.

    1 solenoid valve and 1 water meter for water make-up.

    Cooling insulation with condensation water protection.

    Type
    W
    H
    T
    m
    [kg]
    Pel
    [kW]
    dpu
    [bar]
    SPL
    [dB(A)]
    EAN
    Article No
    10 bar (PS)
    TV 4.2 EHC
    680
    920
    530
    55
    1,5
    1-2,5
    ~55*
    7640161629691
    811 1550
    TV 6.2 EHC
    680
    920
    530
    58
    2,2
    1,5-3,5
    ~55*
    7640161629707
    811 1551
    TV 8.2 EHC
    680
    920
    530
    61
    2,8
    2-4,5
    ~55*
    7640161629714
    811 1552
    TV 10.2 EHC
    680
    1300
    530
    71
    3,4
    3,5-6,5
    ~60*
    7640161629721
    811 1553
    13 bar (PS)
    TV 14.2 EHC
    680
    1300
    530
    98
    3,4
    5,5-10
    ~60*
    7640161629738
    811 1554

    T = Depth of the device

    dpu = Working pressure range

    *) Pump operation

    Expansion vessels, Transfero TU/TU...E

    Primary vessel. Measuring foot for content measurement. Including assembly kit for the water-side connection.

    Transfero TU

    Primary vessel. Measuring foot for content measurement. Including assembly kit for the water-side connection.

    Type
    VN
    [l]
    D
    H
    H***
    m
    [kg]
    S
    EAN
    Article No
    2 bar (PS)
    TU 200
    200
    500
    1339
    1565
    36
    Rp 1 1/4
    7640148631594
    713 1000
    TU 300
    300
    560
    1469
    1690
    41
    Rp 1 1/4
    7640148631600
    713 1001
    TU 400
    400
    620
    1532
    1760
    58
    Rp 1 1/4
    7640148631617
    713 1002
    TU 500
    500
    680
    1627
    1858
    68
    Rp 1 1/4
    7640148631624
    713 1003
    TU 600
    600
    740
    1638
    1873
    78
    Rp 1 1/4
    7640148631631
    713 1004
    TU 800
    800
    740
    2132
    2360
    99
    Rp 1 1/4
    7640148631648
    713 1005

    VN = Nominal volume

    ***) Max. height when vessel is tilted. Tolerance 0 /-100.

    Secondary vessel.Including assembly kit for the water-side connection, flexible hose and lock shield valve with ball valve for fast draining.

    Transfero TU...E

    Secondary vessel.
    Including assembly kit for the water-side connection, flexible hose and lock shield valve with ball valve for fast draining.

    Type
    VN
    [l]
    D
    H
    H***
    m
    [kg]
    S
    EAN
    Article No
    2 bar (PS)
    TU 200 E
    200
    500
    1339
    1565
    35
    Rp 1 1/4
    7640148631655
    713 2000
    TU 300 E
    300
    560
    1469
    1690
    40
    Rp 1 1/4
    7640148631662
    713 2001
    TU 400 E
    400
    620
    1532
    1760
    57
    Rp 1 1/4
    7640148631679
    713 2002
    TU 500 E
    500
    680
    1627
    1868
    67
    Rp 1 1/4
    7640148631686
    713 2003
    TU 600 E
    600
    740
    1638
    1873
    75
    Rp 1 1/4
    7640148631693
    713 2004
    TU 800 E
    800
    740
    2132
    2360
    98
    Rp 1 1/4
    7640148631709
    713 2005

    VN = Nominal volume

    ***) Max. height when vessel is tilted. Tolerance 0 /-100.

    Expansion vessels, Transfero TG/TG...E

    Secondary vessel.Including flexible hose for the water-side connection and lock shield valve with ball valve for fast draining.

    Transfero TG...E

    Secondary vessel.
    Including flexible hose for the water-side connection and lock shield valve with ball valve for fast draining.

    Type *
    VN
    [l]
    D
    H
    H***
    m
    [kg]
    S
    Sw
    EAN
    Article No
    2 bar (PS)
    TG 1000 E
    1000
    850
    2199
    2210
    280
    Rp 1 1/4
    G3/4
    7640148631778
    713 2006
    TG 1500 E
    1500
    1016
    2351
    2381
    360
    Rp 1 1/4
    G3/4
    7640148631785
    713 2007
    TG 2000 E
    2000
    1016
    2848
    2876
    640
    Rp 1 1/4
    G3/4
    7640148631792
    713 2012
    TG 3000 E
    3000
    1300
    2951
    3016
    800
    Rp 1 1/4
    G3/4
    7640148631808
    713 2009
    TG 4000 E
    4000
    1300
    3592
    3633
    910
    Rp 1 1/4
    G3/4
    7640148631815
    713 2010
    TG 5000 E
    5000
    1300
    4216
    4275
    1010
    Rp 1 1/4
    G3/4
    7640148631822
    713 2011

    VN = Nominal volume

    SW = Draining

    *) Special vessel upon request.

    **) Tolerance 0 /-100.

    ***) Max. height when vessel is tilted. Tolerance 0 /-100.

    Primary vessel. Measuring foot for content measurement. Including assembly kit for the water-side connection.

    Transfero TG

    Primary vessel. Measuring foot for content measurement. Including assembly kit for the water-side connection.

    Type *
    VN
    [l]
    D
    H
    H***
    m
    [kg]
    S
    EAN
    Article No
    2 bar (PS)
    TG 1000
    1000
    850
    2199
    2210
    280
    Rp 1 1/4
    7640148631716
    713 1006
    TG 1500
    1500
    1016
    2351
    2381
    360
    Rp 1 1/4
    7640148631723
    713 1007
    TG 2000
    2000
    1016
    2848
    2876
    640
    Rp 1 1/4
    7640148631730
    713 1012
    TG 3000
    3000
    1300
    2951
    3016
    800
    Rp 1 1/4
    7640148631747
    713 1009
    TG 4000
    4000
    1300
    3592
    3633
    910
    Rp 1 1/4
    7640148631754
    713 1010
    TG 5000
    5000
    1300
    4216
    4275
    1010
    Rp 1 1/4
    7640148631761
    713 1011

    VN = Nominal volume

    *) Special vessel upon request.

    **) Tolerance 0 /-100.

    ***) Max. height when vessel is tilted. Tolerance 0 /-100.

    Lock shield valve for buffer vessel

    Female thread on both sides, flat sealing union for direct connection to all suitable expansion vessels.

    Lock shield valve DLV

    Female thread on both sides, flat sealing union for direct connection to all suitable expansion vessels.

    Type
    PS
    [bar]
    L
    m
    [kg]
    S
    SG
    SW
    EAN
    Article No
    DLV 20
    16
    97
    0,49
    Rp3/4
    G3/4
    G3/4
    7640148638579
    535 1434
    DLV 25
    16
    100
    0,54
    Rp1
    G1
    G3/4
    7640148638586
    535 1436
    Buffer vessel

    Cylindrical shape, to be used with the Transfero TV 14 (10 bar < psvs ≤ 13 bar).

    Statico SU

    Cylindrical shape, to be used with the Transfero TV 14 (10 bar < psvs ≤ 13 bar).

    Type
    VN
    [l]
    p0
    [bar]
    D
    H
    H***
    m
    [kg]
    S
    EAN
    Article No
    10 bar (PS)
    SU 140.10
    140
    4
    420
    1274
    1489
    32
    R3/4
    7640148630290
    710 3007
    Type
    VN
    [l]
    p0
    [bar]
    D
    H
    m
    [kg]
    S
    EAN
    Article No
    25 bar (PS), 100°C (TS)
    SH 150.25
    150
    4
    500
    1070
    71
    R1 1/4
    7640161636989
    301012-01300
    SH 300.25
    300
    4
    640
    1323
    126
    R1 1/4
    7640161637160
    301012-01600

    VN = Nominal volume

    **) Tolerance 0 /+35

    Discus shaped

    Statico SD

    Discus shaped

    Type
    VN
    [l]
    p0
    [bar]
    D
    H
    m
    [kg]
    S
    EAN
    Article No
    Transfero TV 4,6,8
    SD 50.10
    50
    4
    536
    316**
    12
    R3/4
    7640148630139
    710 3005
    Transfero TV 10, 14 (psvs ≤ 10 bar)
    SD 80.10
    80
    4
    636
    346**
    16
    R3/4
    7640148630146
    710 3006
    Pleno P water make-up modules

    Hydraulic unit for water make up operation with Vento/Transfero Connect. Consists of Pleno P BA4 R back flow preventer and Pleno P AB5 modules, with protection class 5 according to EN 1717.

    Pleno P AB5 R

    Hydraulic unit for water make up operation with Vento/Transfero Connect. Consists of Pleno P BA4 R back flow preventer and Pleno P AB5 modules, with protection class 5 according to EN 1717.

    Type
    PS
    [bar]
    T
    H1
    H2
    m
    [kg]
    qwm
    [l/h]
    EAN
    Article No
    AB5 R
    10
    220
    280
    1000
    3,8
    200
    7640161630161
    813 3330

    qwm = make-up water flow

    T = Depth of the device

    Hydraulic unit for water make up operation with Vento/Transfero Connect. Consists of a breaktank type AB (protection class 5) according EN 1717. For installation on the back of each unit. Can be used for 3rd party softening modules which do not fulfil the requirement of qwm min 1300 l/h and therefore cannot be directly connected.

    Pleno P AB5

    Hydraulic unit for water make up operation with Vento/Transfero Connect. Consists of a breaktank type AB (protection class 5) according EN 1717. For installation on the back of each unit. Can be used for 3rd party softening modules which do not fulfil the requirement of qwm min 1300 l/h and therefore cannot be directly connected.

    Type
    PS
    [bar]
    T
    H1
    H2
    m
    [kg]
    qwm
    [l/h]
    EAN
    Article No
    AB5
    10
    220
    280
    1000
    1,83
    200
    7640161630154
    813 3320

    Hydraulic unit for water make-up operation with Vento/Transfero Connect, Pleno PX/PIX, Simply Compresso C 2.1-80 SWM, and in combination with Pleno Refill modules. Features a shut off valve, check valve, filter and a type BA backflow preventer (protection class 4) according to EN 1717.Connection (Swm): G1/2

    Pleno P BA4 R

    Hydraulic unit for water make-up operation with Vento/Transfero Connect, Pleno PX/PIX, Simply Compresso C 2.1-80 SWM, and in combination with Pleno Refill modules. Features a shut off valve, check valve, filter and a type BA backflow preventer (protection class 4) according to EN 1717.
    Connection (Swm): G1/2

    Type
    PS
    [bar]
    W
    L
    H
    m
    [kg]
    qwm
    [l/h]
    EAN
    Article No
    BA4 R
    10
    210
    1300
    135
    1,1
    350*
    250**
    50***
    q(pw-pout) ****
    7640161630147
    813 3310

    * maximum average value for make-up water degassing with Vento V/VI and Transfero TV/TVI
    ** maximum average value for make-up water degassing with Vento Compact
    *** when using flow limiter for operation with low flow water treatment cartridges
    **** for combination with Pleno PX/PIX see q(pw-pout) diagram in Pleno Connect datasheet

    Pleno Refill

    Hydraulic unit for water demineralisation together with Vento/Transfero Connect TecBoxes. Filter with 25 µm mesh size to protect the hydronic system. Desalination bottle filled with high grade resin.

    Pleno Refill Demin

    Hydraulic unit for water demineralisation together with Vento/Transfero Connect TecBoxes. Filter with 25 µm mesh size to protect the hydronic system. Desalination bottle filled with high grade resin.

    3/4" swivelling nut, 3/4" external thread suitable for flat gasket.
    Nominal pressure: PS 8
    Max. working temperature: 45°C
    Min. working temperature: > 4°C

    Type
    Capacity
    l x °dH
    Sin
    Sout
    D
    H
    L
    m
    [kg]
    EAN
    Article No
    Refill Demin 13500
    13500
    G3/4
    G3/4
    220
    466
    455
    13
    7640161630505
    813 3260
    Refill Demin 18000
    18000
    G3/4
    G3/4
    270
    458
    455
    16,2
    7640161630512
    813 3270

    → = Flow direction

    Hydraulic unit for water softening together with Vento/Transfero Connect TecBoxes. Filter with 25 µm mesh size to protect the hydronic system. Softening bottle filled with high grade resin.

    Pleno Refill

    Hydraulic unit for water softening together with Vento/Transfero Connect TecBoxes. Filter with 25 µm mesh size to protect the hydronic system. Softening bottle filled with high grade resin.

    3/4" swivelling nut, 3/4" external thread suitable for flat gasket.
    Nominal pressure: PS 8
    Max. working temperature: 45°C
    Min. working temperature: > 4°C

    Type
    Capacity
    l x °dH
    Sin
    Sout
    D
    H
    L
    m
    [kg]
    EAN
    Article No
    Refill 16000
    16000
    G3/4
    G3/4
    195
    383
    455
    9,1
    7640161630475
    813 3210
    Refill 36000
    36000
    G3/4
    G3/4
    220
    466
    455
    13
    7640161630482
    813 3220
    Refill 48000
    48000
    G3/4
    G3/4
    270
    458
    455
    16,2
    7640161630499
    813 3230

    7132006

    Select a format Download

    7132000

    Select a format Download

    7131007

    Select a format Download

    7131004

    Select a format Download

    7131000

    Select a format Download

    7131003

    Select a format Download

    7131010

    Select a format Download

    Pleno_P_AB5_813_3320

    Select a format Download

    7131009

    Select a format Download

    7131006

    Select a format Download

    7131001

    Select a format Download

    7131005

    Select a format Download

    Transfero_TV_Connect_front

    Select a format Download

    7131011

    Select a format Download

    Transfero_TV_Connect

    Select a format Download

    7131002

    Select a format Download

    Pleno_P_AB5R_813_3330

    Select a format Download

    2D3D