Technical description
Applications:
Heating, solar and chilled water systems.
Media:
Non-aggressive and non-toxic system media.
Addition of antifreeze agent up to 50%.
Pressure:
Min. admissible pressure, PSmin: 0 bar
Max. admissible pressure, PS: see Articles
Temperature:
Max. admissible bag temperature, TB: 70 °C
Min. admissible bag temperature, TBmin: 5 °C
Material:
Steel. Color beryllium.
Lock shield valve DLV: Brass
Airproof butyl bag according to EN 13831 and Pneumatex internal standard.
Transportation and storage:
In frostless, dry places.
Standard:
Constructed according to PED 2014/68/EU.
Warranty:
Statico SD, SU: 5-year warranty for the vessel.
Statico SG: 5-year warranty for the airproof butyl bag.
Technical description – Lock shield valve
Applications:
Heating, solar and cooling water systems.
Deployment in systems according to EN 12828.
Media:
Non-aggressive and non-toxic system media.
Addition of antifreeze agent up to 50%.
Functions:
Shut-off. Maintenance and disassembly of expansion vessels.
Pressure:
Min. admissible pressure, PSmin: 0 bar
Max. admissible pressure, PS: 16 bar
Temperature:
Max. admissible temperature, TS: 120 °C
Min. admissible temperature, TSmin: -10 °C
Material:
Brass.
General:
Can only only be closed with the supplied allen key. Ball valve with DN 15 hose connection for fast draining.
Technical description – Manometer
Applications:
Heating, solar and cooling water systems.
Deployment in systems according to EN 12828, SWKI 93-1.
Functions:
Control of the filling pressure at expansion vessels.
Pressure:
Min. admissible pressure, PSmin: 0 bar
Max. admissible pressure, PS: 4 bar
Temperature:
Max. admissible temperature, TS: 60 °C
Min. admissible temperature, TSmin: -10 °C
Technical description – Thermometer/Manometer
Applications:
Heating, solar and cooling water systems.
Deployment in systems according to EN 12828, SWKI 93-1.
Functions:
Control of the filling pressure at expansion vessels.
Pressure:
Min. admissible pressure, PSmin: 0 bar
Max. admissible pressure, PS: 4 bar
Temperature:
Max. admissible temperature, TS: 120 °C
Min. admissible temperature, TSmin: -10 °C
Technical description – Pre-pressure measuring gauge
Applications:
Heating, solar and cooling water systems.
Deployment in systems according to EN 12828, SWKI 93-1.
Functions:
Control of the pre-pressure at expansion vessels. Auto on/off. Automatic calibration.
Pressure:
Min. admissible pressure, PSmin: 0 bar
Max. admissible pressure, PS: 10 bar
Temperature:
Max. admissible temperature, TS: 120 °C
Min. admissible temperature, TSmin: -10 °C
Material:
Rugged plastic housing.