Technical description
Functions:
Proportional control
3-point control
On-off control
Manual override
Stroke detection
Mode, status and position indication
Output signal VDC
Stroke limitation setting
Minimum stroke setting
Valve blockage protection
Valve clogging detection
Error safe position
Diagnostic/Logging
Delayed start-up
Plus version:
With optional BUS communication board
+ ModBus or BACnet
With optional relay board
+ 1 binary input, max. 100 Ω, cable max. 32.8 ft or shielded.
+ 2 relays, max. 5A, 30 VDC/250 VAC on resistive load
+ Output signal in mA
Supply voltage:
24 VAC/VDC ±15%.
100-240 VAC ±10%.
Frequency 50/60 Hz ±3 Hz.
Power consumption:
24 VAC/VDC:
Operation: < 8 VA (VAC); < 4.5 W (VDC)
Standby: < 1 VA (VAC); < 0.5 W (VDC)
100-240 VAC:
Operation: < 9.7 VA (VAC)
Standby: < 1.8 VA (VAC)
Input signal:
0(2)-10 VDC, Ri 47 kΩ.
Adjustable sensitivity 0.1-0.5 VDC.
0.33 Hz low pass filter.
0(4)-20 mA Ri 500 Ω.
Proportional:
0-10, 10-0, 2-10 or 10-2 VDC
0-20, 20-0, 4-20 or 20-4 mA
Proportional split-range:
0-5, 5-0, 5-10 or 10-5 VDC
0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC
2-6, 6-2, 6-10 or 10-6 VDC
0-10, 10-0, 10-20 or 20-10 mA
4-12, 12-4, 12-20 or 20-12 mA
Proportional dual-range (for change-over):
0-3.3 / 6.7-10 VDC,
10-6.7 / 3.3-0 VDC,
2-4.7 / 7.3-10 VDC or
10-7.3 / 4.7-2 VDC.
Default setting: Proportional 0-10 VDC.
Output signal:
0(2)-10 VDC, max. 8 mA, min. 1.25 kΩ.
Plus version:
0(4)-20 mA, max. 700 Ω.
Ranges: See “Input signal”.
Default setting: Proportional 0-10 VDC.
Characteristics:
Linear, EQM 0.25 and inverted EQM 0.25.
Default setting: Linear.
Control speed:
76.2, 101.6, 152.4, 203.2, 304.8 or 406.4 s/in
Default setting: 76.2 s/in.
Adjusting force:
168 lbf
Temperature:
Media temperature: 32°F – +248°F
Operating environment: 32°F – +122°F (5-95%RH, non-condensing)
Storage environment: -4°F – +158°F (5-95%RH, non-condensing)
Ingress protection:
IP54
all directions
(according to EN 60529)
Protection class:
(according to EN 61140).
100-240 VAC: Class I.
24 VAC/VDC: Plus version with optional relay board, Class I.
All other versions, Class III safety extra low voltage.
Stroke:
0.87 in
Automatic detection of the valve lift (stroke detection).
Noise level:
Max. 40 dBA
Weight:
3.5 lb
Connection to valve:
By two M8 screws to the valve and by quick connection to the stem.
Material:
Cover: PBT
Bracket: Alu EN44200
Colour:
Orange RAL 2011, grey RAL 7043.
Marking:
IMI TA, product name, article No. and technical specification.
LED indication description.
Certification CE:
LV-D. 2014/35/EU: EN 60730-1, -2-14.
EMC-D. 2014/30/EU: EN 60730-1, -2-14.
RoHS-D. 2011/65/EU: EN 50581.
Product standard:
EN 60730.
(for Residential and industrial areas)
Cable:
Wire cross-section*: 20 AWG-14 AWG (0.5-2.0 mm2)
- Protection class I: H05VV-F or similar
- Protection class III: LiYY or similar
*) Note: Wire cross-sections must be chosen according to actuator power consumption and line length, such as the voltage supply to the actuator does not go below 20.4 VAC/VDC (24 VAC/VDC minus 15%).
In case of VDC input signal on a 24 VAC/VDC powered actuator, the voltage drop on neutral line must be smaller than the defined hysteresis level for the VDC input signal.