TA-Slider 500 BACnet/Modbus

IMI TA
Compare
​​​​​​​ Digitally configurable proportional push-pull actuator for Bus communication with BACnet MS/TP or Modbus RTU – 500/300 N Digitally configurable actuators for Bus communication with BACnet MS/TP or Modbus RTU, and a wide range of setup options provide extensive flexibility for on-site parameter adaptation. Fully programmable binary input, relay and adjustable max. stroke of the valve bring new opportunities for advanced hydronic control and balancing.

Convenient, reliable setup

Fully customisable by smartphone via Bluetooth using a TA-Dongle.

Fully configurable

More than 200 setup options allow input and output signals, binary input, relay, characteristics and many other parameters to be configured.

Easy diagnostics

Tracks the last 10 errors to allow system faults to be found quickly.

Quick copying of settings

Setup configuration can be copied quickly from the TA-Dongle to identical TA-Slider actuators.

Technical description

Functions:

Proportional control
Manual override
Stroke detection
Mode, status and position indication
Stroke limitation setting
Valve blockage protection
Valve clogging detection
Error safe position
Diagnostic/Logging

BACnet/Modbus version:
+ 1 binary input, max. 100 Ω, cable max. 10 m or shielded.
+ 1 connection for Pt1000 temperature probe.

BACnet/Modbus R24 version:
+ 1 binary input, max. 100 Ω, cable max. 10 m or shielded.
+ 2 connections for Pt1000 temperature probe.
+ 1 relay, max. 2A, 30 VAC/VDC on resistive load.

Supply voltage:

24 VAC/VDC ±15%.
Frequency 50/60 Hz ±3 Hz.

Power consumption:

Operation: < 3.0 VA (VAC); < 1.5 W (VDC)
Standby: < 1.5 VA (VAC); < 0.75 W (VDC)

Input signal:

By BACnet/Modbus or with hybrid control mode;
0(2)-10 VDC, Ri 47 kΩ.
Adjustable hysteresis sensitivity 0.1-0.5 VDC.
0.33 Hz low pass filter.
Proportional:
0-10, 10-0, 2-10 or 10-2 VDC.
Proportional split-range:
0-5, 5-0, 5-10 or 10-5 VDC.
0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC.
2-6, 6-2, 6-10 or 10-6 VDC.
Proportional dual-range (for change-over):
0-3.3 / 6.7-10 VDC,
10-6.7 / 3.3-0 VDC,
2-4.7 / 7.3-10 VDC or
10-7.3 / 4.7-2 VDC.
Default setting: By BACnet/Modbus. If Hybrid mode chosen, default input signal is Proportional 0-10 VDC.

Output signal:

By BACnet/Modbus.

Characteristics:

Linear, EQM 0.25 and inverted EQM 0.25.
Default setting: Linear.

Control speed:

4 or 6 s/mm.
Default setting: 4 s/mm.

Adjusting force:

Push 500 N
Pull 300 N

Temperature:

Media temperature: max. 120°C
Operating environment: 0°C – +50°C (5-95%RH, non-condensing)
Storage environment: -20°C – +70°C (5-95%RH, non-condensing)

Ingress protection:

IP54

(all directions)

(according to EN 60529)

Protection class:

(according to EN 61140)

III (SELV)

Cables:

Separate overmoulded cables (see Additional equipment).
Type LiYCY 5x0.34 mm2 (cables A and B) and type LiYY 6x0.34 mm2 (cable C).
Halogen free, fire class B2ca – s1a, d1, a1 according to EN 50575.
Relay cable (R24 version):
Type LiYY 3x0.34 mm2.
1, 2 or 5 m. With wire end sleeves.
Halogen free, fire class B2ca – s1a, d1, a1 according to EN 50575.

Stroke:

16,2 mm

Automatic detection of the valve lift (stroke detection).

Noise level:

Max. 30 dBA

Weight:

BACnet/Modbus: 0.25 kg
BACnet/Modbus R24:
0.29 kg, 1 m relay cable
0.33 kg, 2 m relay cable
0.47 kg, 5 m relay cable

Connection to valve:

Swivelling nut M30x1,5.

Material:

Cover: PC/ABS GF8
Housing: PA GF40.
Swivelling nut: Nickel-plated brass.

Colour:

White RAL 9016, grey RAL 7047.

Marking:

Label: IMI TA, CE, product name, article No. and technical specification.

Certification CE:

LV-D. 2014/35/EU: EN 60730-1, -2-14.
EMC-D. 2014/30/EU: EN 60730-1, -2-14.
RoHS-D. 2011/65/EU: EN 50581.

Product standard:

EN 60730.

Articles - TA-Slider 500 BACnet/Modbus

TA-Slider 500 BACnet/Modbus

Input signal: Via Bus or 0(2)-10 VDC

With binary input and 1 connection for Pt1000 temperature probe

Bus
EAN
Article No
BACnet
5901688824009
322225-13011
Modbus
5901688823781
322225-12011

Articles - TA-Slider 500 BACnet/Modbus R24

TA-Slider 500 BACnet/Modbus R24

Input signal: Via Bus or 0(2)-10 VDC

With binary input, 2 connections for Pt1000 temperature probe and relay 24V

Relay cable length [m]
Bus
EAN
Article No
With halogen free relay cable
1
BACnet
5901688829059
322225-13314
2
BACnet
5901688829066
322225-13315
5
BACnet
5901688829073
322225-13316
1
Modbus
5901688824092
322225-12314
2
Modbus
5901688824108
322225-12315
5
Modbus
5901688824115
322225-12316

Additional equipment

Daisy chain cables

A: To connect the first TA-Slider 160/500 BACnet or Modbus of a daisy chain to the Bus.
B: Between two actuators in a daisy chain.
C: To enable hybrid mode or provide power supply if the daisy chain is long.

Cable length [m]
EAN
Article No
Halogen free cable
Type A
1,5
5902276898228
322042-80012
5
5902276898235
322042-80013
10
5902276898242
322042-80014
Type B
1,5
5902276898259
322042-80015
5
5902276898266
322042-80016
10
5902276898273
322042-80017
Type C
1,5
5902276898280
322042-80018
5
5902276898297
322042-80019
10
5902276898303
322042-80020

TA-Dongle

For Bluetooth communication with the HyTune app, transfer configuration settings and manual override.

EAN
Article No
5901688828632
322228-00001