Technical description
Applications:
Heating and cooling systems.
Function:
Control
Flow limitation (Eclipse)
Stepless presetting (V-exact II)
Shut-off
Prevents hammering noises with interchanged supply and return pipe
Dimensions:
DN 10-15
Pressure class:
PN 10
Temperature:
Max. working temperature: 120°C, with protection cap or actuator 100°C.
Min. working temperature: -10°C.
Flow range Eclipse:
The flow can be stepless pre-set within the range: 10-150 l/h.
Delivery setting: Commissioning
(Max. nominal flow qmN at 10 kPa respecting EN 215: 115 l/h)
Differential pressure (ΔpV) Eclipse:
Max. differential pressure:
60 kPa (<30 dB(A))
Min. differential pressure:
10 – 100 l/h = 10 kPa
100 – 150 l/h = 15 kPa
Materials:
Valve body: Corrosion resistant Gunmetal
O-rings: EPDM rubber
Valve disc: EPDM rubber
Return spring: Stainless steel
Valve insert: Brass, PPS
The complete thermostatic insert can be replaced using the fitting tool without draining the system.
Spindle: Niro-steel spindle with double O-ring sealing. The outer O-ring can be replaced under pressure (V-exact II).
Surface treatment:
Valve body and fittings are nickel-plated.
Marking:
THE, flow direction arrow, DN and II+ Designation.
With presetting: protection cap white.
Eclipse: Orange protection cap.
Pipe connection:
The female-threaded version is designed for connection to threaded pipe, or in conjunction with compression fittings, to copper precision steel or multi-layer pipe (only DN 15).
Connection to thermostatic head and actuator:
HEIMEIER M30x1,5