Caractéristiques et avantages

    Higher Efficiency Cyclonic vacuum degassing

    Significantly higher efficiency than most other vacuum degassing systems.

    Compact design for floor and wall hanging installation

    Easy Commissioning, Remote Access and Trouble-shooting

    Integrated standard connections to our IMI Webserver and to BMS.

    Optional sound absorbing wall bracket

    For Vento Compact in installations particularly sensitive to structure-borne sound.

    Plug & Play installation and start-up

    Connect unit to the installation
    Plug in power supply
    Follow the instructions displayed on the BrainCube

    Technical description – Control unit TecBox

    Applications:

    Heating systems. For systems according to EN 12828, SWKI HE301-01, EN 12976, ENV 12977, EN 12952, EN 12953

    Media:

    Non-aggressive and non-toxic system media.
    Ethylene or propylene glycol-based antifreeze up to 50%.

    Pressure:

    Min. admissible pressure, PSmin: -1 bar
    Max. admissible pressure, PS: 10 bar

    Temperature:

    Min. admissible temperature, TSmin: 0°C
    Max. admissible temperature, TS: 90°C

    Max. admissible ambient temperature, TA: 40°C
    Min. admissible ambient temperature, TAmin: 0°C

    Supply voltage:

    1 x 230 V (± 10 %) / 50 Hz

    Electrical connections:

    Onsite fuses according to power demand and local norms
    3 potential-free outputs (NO) for external alarm indication (230V max. 2A)
    1 RS 485 In/Output
    1 Ethernet RJ45 plug socket
    1 USB Hub plug socket

    Enclosure class:

    IP54 according to EN 60529

    Mechanical connections:

    Sin1: inlet from the system G1/2"
    Sout: outlet to the system G1/2"

    Material:

    Metal components with medium contact: carbon steel, cast iron, stainless steel, AMETAL®, brass, gunmetal.

    Transportation and storage:

    In frostless, dry places.

    Standard:

    Constructed according to
    LV-D. 2014/35/EU
    EMC-D. 2014/30/EU

    Control unit TecBox, Simply Vento Heating

    Simply Vento

    Cyclonic vacuum degassing unit. 1 pump, cyclonic vacuum degassing unit and BrainCube Connect control.

    2 connection hoses with ball valves. Connections G1/2"

    Type
    B
    H
    T
    m
    [kg]
    Pel
    [kW]
    VNd
    [m3]
    SPL
    [dB(A)]
    dpu
    [bar]
    EAN
    Article No
    10 bar (PS)
    V 2.1 S
    520
    575
    350
    30
    0,75
    10
    ~55*
    0,5 - 2,5
    7640161642287
    303030-10400

    T = Depth of the device

    VNd = Water capacity for which a device is rated

    Pel = Electric load

    dpu = Working pressure range

    *) Pump operation

    Sound absorbing wall bracket for Vento VS/VF Connect

    Wall bracket WB VSF

    Sound-absorbing wall bracket for Simply Vento Connect and Vento Compact Connect.
    Reliably reduces the transmission of structure-borne sound from the unit to the mounting wall to a minimum.

    Type
    B
    H
    T
    m
    [kg]
    EAN
    WB VSF
    376
    500
    520
    7,5
    7640161644557
    301032-30021

    B = Centre-to-centre distance for optimum mounting

    Vento_V_Connect_front_kat

    Sélectionnez un format Télécharger

    Simply_Vento_V2_1_SWME

    Sélectionnez un format Télécharger

    Vento_Connect_2020

    Sélectionnez un format Télécharger

    Vento_VI_Connect

    Sélectionnez un format Télécharger

    Vento_V_Connect

    Sélectionnez un format Télécharger

    Simply_Vento_V2_1_S

    Sélectionnez un format Télécharger