Features & Benefits

    Make-up water limitation

    Automatic limitation of make-up water with the help of the PNEUMATEX BrainCube control unit.

    BrainCube control

    Self-optimising with memory function (PI, PI 6, PI 9).

    Technical description

    Application:

    Heating, solar and chilled water systems.
    For systems according to EN 12828, EN 12976, ENV 12977, EN 12952, EN 12953.

    Media:

    Entry: potable water
    Outflow(Consumer side): Non-aggressive and non-toxic system media.
    Addition of antifreeze agent up to 50%.

    Pressure:

    Min. admissible pressure, PSmin: 0 bar
    Max. admissible pressure, PS: see Articles

    Temperature:

    Max. admissible temperature, TS: 65 °C (PX, PIX), 30 °C (PI9, PI9F)
    Min. admissible temperature, TSmin: 0 °C
    Max. admissible ambient temperature, TA: 40 °C

    Supply voltage:

    1 x 230 V (± 10 %) / 50 Hz

    Electrical connections:

    Pleno PIX, PI9(F):
    Onsite fuses according to power demand and local norms
    4 potential free outputs (NO) for external alarm indication (230V max. 2A)
    1 RS 485 In/Output
    1 Ethernet RJ45 plug socket
    1 USB Hub plug socket

    Enclosure class:

    Pleno PX: IP 65
    Pleno PIX: IP 54
    Pleno PI9(F): IP 54

    Material:

    Metal components with medium contact:
    carbon steel, cast iron, stainless steel,
    brass, and gunmetal.

    Standard:

    Pleno PIX, PI9(F):
    Constructed according to
    LV-D. 2014/35/EU
    EMC-D. 2014/30/EU
    Pleno P BA4 R: EN1717 (protection class 4)

    Control unit TecBox, Pleno PX

    Hydraulic unit for water make-up operation with Compresso Connect. Water make-up without pumps. 1 solenoid valve, 1 electronic water meter, connection for Pleno P BA4 R.Connection in (Swm): G3/4.Connection out (Sout): G1/2.

    Pleno PX

    Hydraulic unit for water make-up operation with Compresso Connect. Water make-up without pumps. 1 solenoid valve, 1 electronic water meter, connection for Pleno P BA4 R.
    Connection in (Swm): G3/4.
    Connection out (Sout): G1/2.

    Type
    PS
    [bar]
    B
    H
    T
    m
    [kg]
    Pel
    [kW]
    Kvs
    EAN
    Article No
    PX
    10
    198
    356
    150
    1,5
    0,02
    1,4
    7640161641792
    301060-10011

    T = Depth of the device

    Pel = Electric load

    Control unit TecBox, Pleno PIX Connect

    Control unit TecBox. Water make-up without pumps. 1 solenoid valve, 1 electronic water meter, connection for Pleno P BA4 R, BrainCube control.Connection in (Swm): G3/4.Connection out (Sout): G1/2.

    Pleno PIX Connect

    Control unit TecBox. Water make-up without pumps. 1 solenoid valve, 1 electronic water meter, connection for Pleno P BA4 R, BrainCube control.
    Connection in (Swm): G3/4.
    Connection out (Sout): G1/2.

    Type
    PS
    [bar]
    B
    H
    T
    m
    [kg]
    Pel
    [kW]
    Kvs
    EAN
    Article No
    PIX
    10
    198
    392
    190
    4,3
    0,04
    1,4
    5901688829851
    301060-20001

    T = Depth of the device

    Pel = Electric load

    Water make-up protection module

    Hydraulic unit for water make-up operation with Vento/Transfero Connect, Pleno PX/PIX, Simply Compresso C 2.1-80 SWM, and in combination with Pleno Refill modules. Features a shut off valve, check valve, filter and a type BA backflow preventer (protection class 4) according to EN 1717.Connection (Swm): G1/2

    Pleno P BA4 R

    Hydraulic unit for water make-up operation with Vento/Transfero Connect, Pleno PX/PIX, Simply Compresso C 2.1-80 SWM, and in combination with Pleno Refill modules. Features a shut off valve, check valve, filter and a type BA backflow preventer (protection class 4) according to EN 1717.
    Connection (Swm): G1/2

    Type
    PS
    [bar]
    B
    L
    H
    m
    [kg]
    qwm
    [l/h]
    EAN
    Article No
    BA4 R
    10
    210
    1300
    135
    1,1
    350*
    250**
    50***
    q(pw-pout) ****
    7640161630147
    813 3310

    qwm = make-up water flow

    * maximum average value for make-up water degassing with Vento V/VI and Transfero TV/TVI
    ** maximum average value for make-up water degassing with Vento Compact
    *** when using flow limiter for operation with low flow water treatment cartridges
    **** for combination with Pleno PX/PIX see q(pw-pout) diagram in Pleno Connect datasheet

    T = Depth of the device

    Control unit TecBox, Pleno PI 9 F Connect

    Control unit TecBox. Water make-up with pumps.1 pump, 1 electronic water meter, integrated wall mounting bracket. Integrated break tank type AB5.Connection in (Swm): G1/2Connection out (Sout): G3/4

    Pleno PI 9.1 F Connect

    Control unit TecBox. Water make-up with pumps.
    1 pump, 1 electronic water meter, integrated wall mounting bracket.
    Integrated break tank type AB5.
    Connection in (Swm): G1/2
    Connection out (Sout): G3/4

    Type
    PS
    [bar]
    B
    H
    T
    m
    [kg]
    Pel
    [kW]
    SPL
    [dB(A)]
    dpu
    [bar]
    qwm
    [l/h]
    EAN
    Article No
    PI 9.1 F
    10
    520
    500
    350
    26,5
    0,75
    74
    1-8
    100-450 *)
    5901688829868
    301060-50002

    T = Depth of the device

    Pel = Electric load

    dpu = Working pressure range

    qwm = Water make-up flow

    *) depending on pressure values at Swm and Sout

    Control unit TecBox, Pleno PI 9 Connect

    Control unit TecBox. Water make-up with pumps.2 pumps (one for reserve), 1 electronic water meter. Floor standing.Integrated break tank type AB5.Connection in (Swm): G1/2Connection out (Sout): G3/4

    Pleno PI 9.2 Connect

    Control unit TecBox. Water make-up with pumps.
    2 pumps (one for reserve), 1 electronic water meter. Floor standing.
    Integrated break tank type AB5.
    Connection in (Swm): G1/2
    Connection out (Sout): G3/4

    Type
    PS
    [bar]
    B
    H
    T
    m
    [kg]
    Pel
    [kW]
    SPL
    [dB(A)]
    dpu
    [bar]
    qwm
    [l/h]
    EAN
    Article No
    PI 9.2
    10
    520
    1056
    350
    38
    0,75
    74
    1-8
    100-450 *)
    5901688829882
    301060-40002

    T = Depth of the device

    Pel = Electric load

    dpu = Working pressure range

    qwm = Water make-up flow

    *) depending on pressure values at Swm and Sout

    Control unit TecBox. Water make-up with pumps.1 pump, 1 electronic water meter. Floor standing.Integrated break tank type AB5.Connection in (Swm): G1/2Connection out (Sout): G3/4

    Pleno PI 9.1 Connect

    Control unit TecBox. Water make-up with pumps.
    1 pump, 1 electronic water meter. Floor standing.
    Integrated break tank type AB5.
    Connection in (Swm): G1/2
    Connection out (Sout): G3/4

    Type
    PS
    [bar]
    B
    H
    T
    m
    [kg]
    Pel
    [kW]
    SPL
    [dB(A)]
    dpu
    [bar]
    qwm
    [l/h]
    EAN
    Article No
    PI 9.1
    10
    520
    1056
    350
    27,5
    0,75
    74
    1-8
    100-450 *)
    5901688829875
    301060-30003

    T = Depth of the device

    Pel = Electric load

    dpu = Working pressure range

    qwm = Water make-up flow

    *) depending on pressure values at Swm and Sout

    Pleno Refill 6000, 12000 / Pleno Refill Demin 2000, 4000

    3/4” swivelling nut, 3/4” external thread suitable for flat gasket, with flow limiter. In compliance with SWKI-BT-102-1.

    Demineralisation unit with wall mounting bracket and 25 µm filter

    3/4” swivelling nut, 3/4” external thread suitable for flat gasket, with flow limiter. In compliance with SWKI-BT-102-1.

    Type
    Capacity
    l x °dH
    Sin
    Sout
    H
    L1
    L2
    m
    [kg]
    EAN
    Article No
    Refill Demin 2000 filter
    2000
    G3/4
    G3/4
    571
    366
    271
    4,1
    813 3015
    Refill Demin 4000 filter
    4000
    G3/4
    G3/4
    571
    513
    420
    7,8
    813 3016

    → = Flow direction

    3/4” swivelling nut, 3/4” external thread suitable for flat gasket, with flow limiter.

    Softening unit with wall mounting bracket and 25 µm filter

    3/4” swivelling nut, 3/4” external thread suitable for flat gasket, with flow limiter.

    Type
    Capacity
    l x °dH
    Sin
    Sout
    H
    L1
    L2
    m
    [kg]
    EAN
    Article No
    Refill 6000 filter
    6000
    G3/4
    G3/4
    644
    366
    271
    4,6
    7640153570864
    813 3010
    Refill 12000 filter
    12000
    G3/4
    G3/4
    644
    513
    420
    8,3
    7640161631946
    813 3011

    → = Flow direction

    Pleno Refill 16000, 36000, 48000 / Pleno Refill Demin 13500, 18000

    Demineralisation unit

    3/4" swivelling nut, 3/4" external thread suitable for flat gasket.
    Nominal pressure: PS 8
    Max. working temperature: 45°C
    Min. working temperature: > 4°C

    Type
    Capacity
    l x °dH
    Sin
    Sout
    D
    H
    L
    m
    [kg]
    EAN
    Article No
    Refill Demin 13500
    13500
    G3/4
    G3/4
    220
    466
    455
    13
    7640161630505
    813 3260
    Refill Demin 18000
    18000
    G3/4
    G3/4
    270
    458
    455
    16,2
    7640161630512
    813 3270

    → = Flow direction

    Softening unit

    3/4" swivelling nut, 3/4" external thread suitable for flat gasket.
    Nominal pressure: PS 8
    Max. working temperature: 45°C
    Min. working temperature: > 4°C

    Type
    Capacity
    l x °dH
    Sin
    Sout
    D
    H
    L
    m
    [kg]
    EAN
    Article No
    Refill 16000
    16000
    G3/4
    G3/4
    195
    383
    455
    9,1
    7640161630475
    813 3210
    Refill 36000
    36000
    G3/4
    G3/4
    220
    466
    455
    13
    7640161630482
    813 3220
    Refill 48000
    48000
    G3/4
    G3/4
    270
    458
    455
    16,2
    7640161630499
    813 3230

    → = Flow direction

    30106050002

    Select a format Download

    30106030003

    Select a format Download

    Pleno_Connect_cover

    Select a format Download

    30106020001

    Select a format Download

    30106040002

    Select a format Download

    30106050002_front

    Select a format Download

    30106040002_front

    Select a format Download

    Pleno_P_8133310

    Select a format Download

    Pleno_PX

    Select a format Download

    30106030003_front

    Select a format Download