Features & Benefits
Convenient, reliable setup
Fully customisable by smartphone via Bluetooth using a TA-Dongle.
Fully configurable
More than 200 setup options allow input and output signals, binary input, relay, characteristics and many other parameters to be configured.
Easy diagnostics
Tracks the last 10 errors to allow system faults to be found quickly.
Quick copying of settings
Setup configuration can be copied quickly from the TA-Dongle to identical TA-Slider actuators.
Technical Information
Functions:
Proportional control
Manual override (TA-Dongle)
Stroke detection
Self-adjusting force
Mode, status and position indication
Stroke limitation setting
Minimum stroke setting
Valve blockage protection
Valve clogging detection
Error safe position
Diagnostic/Logging
Delayed start-up
I/O version:
+ 1 binary input, max. 100 Ω, cable max. 10 m or shielded.
+ Output signal
Plus version:
+ 1 binary input, max. 100 Ω, cable max. 10 m or shielded.
+ 1 relay, max. 5A, 30 VDC/250 VAC on resistive load
+ Output signal
CO (change-over) version:
+ 1 binary input, max. 100 Ω, cable max. 10 m or shielded.
+ 1 relay, internally wired for control of TA-M106 actuator on TA-6-way valve (max. 2A, 30 VAC on resistive load).
+ Output signal
Supply voltage:
24 VAC/VDC ±15%.
Frequency 50/60 Hz ±3 Hz.
CO version:
24 VAC ±15%.
Frequency 50/60 Hz ±3 Hz.
Power consumption:
Operation: < 1.0 VA (VAC); < 0.6 W (VDC)
Standby: < 0.5 VA (VAC); < 0.25 W (VDC)
I/O, CO versions:
Operation: < 1.3 VA (VAC); < 0.7 W (VDC)
Standby: < 0.5 VA (VAC); < 0.25 W (VDC)
Plus version:
Operation: < 1.8 VA (VAC); < 1.0 W (VDC)
Standby: < 0.5 VA (VAC); < 0.25 W (VDC)
CO version: TA-M106 actuator consumption must be added separately.
Input signal:
0(2)-10 VDC, Ri 47 kΩ.
Adjustable hysteresis sensitivity 0.1-0.5 VDC.
0.33 Hz low pass filter.
Proportional:
0-10, 10-0, 2-10 or 10-2 VDC.
Proportional split-range:
0-5, 5-0, 5-10 or 10-5 VDC.
0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC.
2-6, 6-2, 6-10 or 10-6 VDC.
Proportional dual-range (for change-over):
0-3.3 / 6.7-10 VDC,
2-4.7 / 7.3-10 VDC,
0-4.5 / 5.5-10 VDC or
2-5.5 / 6.5-10 VDC.
Default setting: Proportional 0-10 VDC.
Output signal:
I/O, Plus, CO versions:
0(2)-10 VDC, max. 8 mA, min. 1.25 kΩ.
Ranges: See “Input signal”.
Default setting: Proportional 0-10 VDC.
Characteristics:
Linear, EQM 0.25 and inverted EQM 0.25.
Default setting: Linear.
Control speed:
10 s/mm
Adjusting force:
160/200 N
Self-adjusting for IMI Hydronic Engineering valves.
Temperature:
Media temperature: max. 120°C
Operating environment: 0°C – +50°C (5-95%RH, non-condensing)
Storage environment: -20°C – +70°C (5-95%RH, non-condensing)
Ingress protection:
IP54
all directions
(according to EN 60529)
Protection class:
(according to EN 61140)
III (SELV) TA-Slider 160, 160 I/O, 160 CO
II TA-Slider 160 Plus (protective insulation)
Cable:
1, 2 or 5 m. With wire end sleeves.
Halogen free as option, fire class B2ca – s1a, d1, a1 according to EN 50575.
TA-Slider 160: type LiYY, 3x0.25 mm2.
TA-Slider 160 I/O: type LiYY, 5x0.25 mm2.
TA-Slider 160 Plus: type LiYY, 5x0.25 mm2 and relay cable type H03VV-F, 3x0.75 mm2, with wire end sleeves.
TA-Slider 160 CO: type LiYY, 5x0.25 mm2 and relay cable type LiYY, 3x0.34 mm2, with connector to actuator TA-M106.
Stroke:
6,9 mm
Automatic detection of the valve lift (stroke detection).
Noise level:
Max. 30 dBA
Weight:
TA-Slider 160, I/O:
0.20 kg, 1 m cable.
0.25 kg, 2 m cable.
0.38 kg, 5 m cable.
TA-Slider 160 Plus:
0.28 kg, 1 m cables.
0.38 kg, 2 m cables.
0.67 kg, 5 m cables.
TA-Slider 160 CO:
0.32 kg, 1 m/1.5 m cables.
0.37 kg, 2 m/1.5 m cables.
0.50 kg, 5 m/1.5 m cables.
Connection to valve:
Swivelling nut M30x1,5.
Material:
Cover: PC/ABS GF8
Housing: PA GF40.
Swivelling nut: Nickel-plated brass.
Colour:
White RAL 9016, grey RAL 7047.
Marking:
Label: IMI TA, CE, product name, article No. and technical specification.
Certification CE:
LV-D. 2014/35/EU: EN 60730-1, -2-14.
EMC-D. 2014/30/EU: EN 60730-1, -2-14.
RoHS-D. 2011/65/EU: EN 63000.
Product standard:
EN 60730
Articles
TA-Slider 160
Input signal: 0(2)-10 VDC
Cable length [m] | Supply voltage | EAN | Article No | |
1 | 24 VAC/VDC | 5901688828397 | 322224-10111 | |
2 | 24 VAC/VDC | 5901688828403 | 322224-10112 | |
5 | 24 VAC/VDC | 5901688828410 | 322224-10113 | |
With halogen free cable | ||||
1 | 24 VAC/VDC | 5901688828427 | 322224-10114 | |
2 | 24 VAC/VDC | 5901688828434 | 322224-10115 | |
5 | 24 VAC/VDC | 5902276883323 | 322224-10116 |
TA-Slider 160 I/O
Input signal: 0(2)-10 VDC
With binary input, VDC output signal
Cable length [m] | Supply voltage | EAN | Article No | |
1 | 24 VAC/VDC | 5902276895951 | 322224-10411 | |
2 | 24 VAC/VDC | 5902276895968 | 322224-10412 | |
5 | 24 VAC/VDC | 5902276895975 | 322224-10413 | |
With halogen free cable | ||||
1 | 24 VAC/VDC | 5902276895982 | 322224-10414 | |
2 | 24 VAC/VDC | 5902276895999 | 322224-10415 | |
5 | 24 VAC/VDC | 5902276896002 | 322224-10416 |
TA-Slider 160 Plus
Input signal: 0(2)-10 VDC
With binary input, relay, VDC output signal
Cable length [m] | Supply voltage | EAN | Article No | |
1 | 24 VAC/VDC | 5902276883330 | 322224-10211 | |
2 | 24 VAC/VDC | 5902276883347 | 322224-10212 | |
5 | 24 VAC/VDC | 5902276883354 | 322224-10213 | |
With halogen free cable | ||||
1 | 24 VAC/VDC | 5902276883361 | 322224-10214 | |
2 | 24 VAC/VDC | 5902276883378 | 322224-10215 | |
5 | 24 VAC/VDC | 5902276883385 | 322224-10216 |
TA-Slider 160 CO
Input signal: 0(2)-10 VDC
With binary input, relay with connector to TA-M106 actuator, VDC output signal
Cable length [m] | Relay cable length* [m] | EAN | Article No | |
1 | 1,5 | 5901688823477 | 322224-10511 | |
2 | 1,5 | 5901688823484 | 322224-10512 | |
5 | 1,5 | 5901688823491 | 322224-10513 | |
With halogen free cable | ||||
1 | 1,5 | 5901688823507 | 322224-10514 | |
2 | 1,5 | 5901688823514 | 322224-10515 | |
5 | 1,5 | 5901688823521 | 322224-10516 |
*) 1,5 m cable length for TA-M106 gives a total cable length of 3 m for all models.
For Bluetooth communication with the HyTune app, transfer configuration settings and manual override.
TA-Dongle
For Bluetooth communication with the HyTune app, transfer configuration settings and manual override.
EAN | Article No |
5901688828632 | 322228-00001 |