Features & Benefits

    Self-sealing measuring points

    Enables TA Link to be fitted snugly onto the balancing valve’s measuring port in just a few seconds.

    Measuring

    Rapid measurement of differential pressure, enabling quicker troubleshooting.

    Technical description

    Application:

    Heating and cooling systems

    Function:

    Measuring

    Range:

    0-5.8 psi or 0-14.5 psi

    Pressure class:

    PN 25

    Max. differential pressure:

    29 psi or 72.5 psi

    Temperature:

    Max. working temperature: 176°F
    Min. working temperature: 5°F

    Output signal:

    0-10 V or 4-20 mA

    Accurancy:

    <±0.145 psi

    Supply voltage:

    18-33 VDC or 24 VAC +15/-10 % (0-10 V)
    11-33 VDC (4-20 mA)

    Response time:

    < 5 ms

    Protection class:

    IP 65

    Material:

    Sensor housing of stainless steel X8CrNiS18-9 (No 1.4305 EN 10 088-3).
    Ceramic membrane.
    EPDM seal.

    Articles

    TA Link

    Range
    EAN
    Article No
    0-10 V
    0-5.8 psi
    7318792750106
    52 010-004
    0-14.5 psi
    7318792750205
    52 010-010
    4-20 mA
    0-14.5 psi
    7318793746207
    52 110-010
    Accessories

    For connection of Ø0.25 in. copper pipe while permitting simultaneous use of our balancing instrument.

    Measuring point, two-way

    For connection of Ø0.25 in. copper pipe while permitting simultaneous use of our balancing instrument.

    EAN
    Article No
    7318792813306
    52 179-100

    Capillary pipe

    L [in]
    EAN
    Article No
    39.4
    7318792750304
    52 010-901

    TA_Link_persp_kat

    Select a format Download

    TA_Link

    Select a format Download

    52179100

    Select a format Download

    Drawings