Features & Benefits
Integrated flow limiter
Eliminates over flows
Easy adjustment
Just a twist to reach design flow
Wide flow range
For high flexibility
Technical Information
Applications:
Heating and cooling systems.
Function:
Control
Flow limitation
Shut-off
Pressure class:
PN 10
Temperature:
Max. working temperature: 120°C
Min. working temperature: -10°C
Flow range:
The flow can be stepless pre-set within the range: 30-300 l/h.
Delivery setting: Commissioning setting.
Max. 2,5 m3/h per heating circuit manifold.
Differential pressure (ΔpV):
Max. differential pressure:
60 kPa (<30 dB(A))
Min. differential pressure:
30 – 150 l/h = 17 kPa
150 – 300 l/h = 25 kPa
Materials:
Thermostatic insert: Brass, PPS (polyphenylsulphide) and SPS (syndiotactic polystyrene)
O-rings: EPDM
Valve disc: EPDM
Spring: Stainless steel
Spindle: Niro-steel spindle with double O-ring seal. The outer O-ring is replaceable under pressure.
Connection fitting: Nickel-plated brass
Connection to thermostatic head and actuator:
HEIMEIER M30x1,5
Articles
With automatic flow limiter.
Eclipse HF thermostatic insert for manifolds, OEM
With automatic flow limiter.
EAN | Article No |
4024052037827 | 9345-00.300 |
*) Valve closed
Subject to technical modifications of the radiator manufacturer.
With automatic flow limiter.
Eclipse HF thermostatic insert for manifolds, manifold height 35-42 mm, OEM
With automatic flow limiter.
EAN | Article No | |
with connection fitting | 4024052978014 | 9340-00.301 |
without connection fitting | 4024052978113 | 9340-00.302 |
for Eclipse. Color orange.
Setting key
for Eclipse. Color orange.
EAN | Article No |
4024052937714 | 3930-02.142 |