Features & Benefits
Convenient, reliable setup
Fully customisable by smartphone via Bluetooth using a TA-Dongle.
Fully configurable
More than 200 setup options allow input and output signals, binary input, relay, characteristics and many other parameters to be configured.
Easy diagnostics
Tracks the last 10 errors to allow system faults to be found quickly.
Quick copying of settings
Setup configuration can be copied quickly from the TA-Dongle to identical TA-Slider actuators.
Technical Information
Functions:
Proportional control
Manual override (TA-Dongle)
Stroke detection
Mode, status and position indication
Stroke limitation setting
Minimum stroke setting
Valve blockage protection
Valve clogging detection
Error safe position
Diagnostic/Logging
Delayed start-up
BACnet/Modbus version:
+ 1 binary input, max. 100 Ω, cable max. 10 m or shielded.
+ 2 connections for Pt1000 temperature probe.
BACnet/Modbus R24 version:
+ 1 binary input, max. 100 Ω, cable max. 10 m or shielded.
+ 2 connections for Pt1000 temperature probe.
+ 1 relay, max. 2A, 30 VAC/VDC on resistive load.
Supply voltage:
24 VAC/VDC ±15%.
Frequency 50/60 Hz ±3 Hz.
Power consumption:
Operation: < 3.0 VA (VAC); < 1.5 W (VDC)
Standby: < 1.5 VA (VAC); < 0.75 W (VDC)
Input signal:
By BACnet/Modbus or with hybrid control mode;
0(2)-10 VDC, Ri 47 kΩ.
Adjustable hysteresis sensitivity 0.1-0.5 VDC.
0.33 Hz low pass filter.
Proportional:
0-10, 10-0, 2-10 or 10-2 VDC.
Proportional split-range:
0-5, 5-0, 5-10 or 10-5 VDC.
0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC.
2-6, 6-2, 6-10 or 10-6 VDC.
Proportional dual-range (for change-over):
0-3.3 / 6.7-10 VDC,
10-6.7 / 3.3-0 VDC,
2-4.7 / 7.3-10 VDC or
10-7.3 / 4.7-2 VDC.
Default setting: By BACnet/Modbus. If Hybrid mode chosen, default input signal is Proportional 0-10 VDC.
Output signal:
By BACnet/Modbus.
Characteristics:
Linear, EQM 0.25 and inverted EQM 0.25.
Default setting: Linear.
Control speed:
4 or 6 s/mm.
Default setting: 4 s/mm.
Adjusting force:
Push 500 N
Pull 300 N
Temperature:
Media temperature: max. 120°C
Operating environment: 0°C – +50°C (5-95%RH, non-condensing)
Storage environment: -20°C – +70°C (5-95%RH, non-condensing)
Ingress protection:
IP54
all directions
(according to EN 60529)
Protection class:
(according to EN 61140)
III (SELV)
Cables:
Separate overmoulded cables (see Additional equipment).
Type LiYCY 5x0.34 mm2 (cables A and B) and type LiYY 6x0.34 mm2 (cable C).
Halogen free, fire class B2ca – s1a, d1, a1 according to EN 50575.
Relay cable (R24 version):
Type LiYY 3x0.34 mm2.
1, 2 or 5 m. With wire end sleeves.
Halogen free, fire class B2ca – s1a, d1, a1 according to EN 50575.
Stroke:
16,2 mm
Automatic detection of the valve lift (stroke detection).
Noise level:
Max. 30 dBA
Weight:
BACnet/Modbus: 0.25 kg
BACnet/Modbus R24:
0.29 kg, 1 m relay cable
0.33 kg, 2 m relay cable
0.47 kg, 5 m relay cable
Connection to valve:
Swivelling nut M30x1,5.
Material:
Cover: PC/ABS GF8
Housing: PA GF40.
Swivelling nut: Nickel-plated brass.
Colour:
White RAL 9016, grey RAL 7047.
Marking:
Label: IMI TA, CE, product name, article No. and technical specification.
Certification CE:
LV-D. 2014/35/EU: EN 60730-1, -2-14.
EMC-D. 2014/30/EU: EN 60730-1, -2-14.
RoHS-D. 2011/65/EU: EN 50581.
Product standard:
EN 60730
Articles
TA-Slider 500 BACnet/Modbus
Input signal: Via Bus or 0(2)-10 VDC

With binary input and 2 connections for Pt1000 temperature probe
Bus | EAN | Article No |
BACnet | 5901688824009 | 322225-13011 |
Modbus | 5901688823781 | 322225-12011 |
TA-Slider 500 BACnet/Modbus R24
Input signal: Via Bus or 0(2)-10 VDC

With binary input, 2 connections for Pt1000 temperature probe and relay 24V
Relay cable length [m] | Bus | EAN | Article No | |
With halogen free relay cable | ||||
1 | BACnet | 5901688829059 | 322225-13314 | |
2 | BACnet | 5901688829066 | 322225-13315 | |
5 | BACnet | 5901688829073 | 322225-13316 | |
1 | Modbus | 5901688824092 | 322225-12314 | |
2 | Modbus | 5901688824108 | 322225-12315 | |
5 | Modbus | 5901688824115 | 322225-12316 |
For Bluetooth communication with the HyTune app, transfer configuration settings and manual override.
TA-Dongle
For Bluetooth communication with the HyTune app, transfer configuration settings and manual override.

EAN | Article No |
5901688828632 | 322228-00001 |
A: To connect the first TA-Slider 160/500 BACnet or Modbus of a daisy chain to the Bus.B: Between two actuators in a daisy chain.C: To enable hybrid mode or provide power supply if the daisy chain is long.
Daisy chain cables
A: To connect the first TA-Slider 160/500 BACnet or Modbus of a daisy chain to the Bus.
B: Between two actuators in a daisy chain.
C: To enable hybrid mode or provide power supply if the daisy chain is long.

Cable length [m] | EAN | Article No | |
Halogen free cable | |||
Type A | |||
1,5 | 5902276898228 | 322042-80012 | |
5 | 5902276898235 | 322042-80013 | |
10 | 5902276898242 | 322042-80014 | |
Type B | |||
1,5 | 5902276898259 | 322042-80015 | |
5 | 5902276898266 | 322042-80016 | |
10 | 5902276898273 | 322042-80017 | |
Type C | |||
1,5 | 5902276898280 | 322042-80018 | |
5 | 5902276898297 | 322042-80019 | |
10 | 5902276898303 | 322042-80020 |
Images

TA-Slider500_BACnet_Modbus_R24_persp
Select a format Download
TA-Slider500_BACnet_Modbus_persp
Select a format Download
TA-Slider500_BACnet_Modbus_persp_R
Select a format Download
TA-Slider500_BACnet_Modbus_front_L
Select a format Download
TA-Slider500_BACnet_Modbus_R24_front_R
Select a format Download
TA-Dongle_persp
Select a format Download
32204280007_cable-C
Select a format Download
32204280004_cable-B
Select a format Download
32204280001_cable-A
Select a format Download
TA-Slider500_BACnet_Modbus_front_R
Select a format Download
TA-Slider500_BACnet_Modbus_R24_front_L
Select a format Download