Features & Benefits

    Fully configurable fail-safe

    Setting of stroke position (extended, retracted or intermediate position) and delay feature for entering/leaving fail-safe mode for a reliable and optimal fail-safe function.

    Convenient, reliable setup

    Fully customisable by smartphone via Bluetooth using a TA-Dongle.

    Fully configurable

    More than 200 setup options allow input and output signals, binary input, relay, characteristics and many other parameters to be configured.

    Easy diagnostics

    Tracks the last 10 errors to allow system faults to be found quickly and health check of fail-safe function.

    Quick copying of settings

    Setup configuration can be copied quickly from the TA-Dongle to identical TA-Slider actuators.

    Technical description

    Functions:

    Electronic fail-safe function
    Proportional control
    Manual override (TA-Dongle)
    Stroke detection
    Mode, status and position indication
    Stroke limitation setting
    Minimum stroke setting
    Valve blockage protection
    Valve clogging detection
    Error safe position
    Diagnostic/Logging
    Delayed start-up

    I/O version:
    + 1 binary input, max. 100 Ω, cable max. 10 m or shielded.
    + Output signal

    R24 version:
    + 1 binary input, max. 100 Ω, cable max. 10 m or shielded.
    + 1 relay, max. 1A, 30 VAC/VDC on resistive load
    + Output signal

    Fail-safe function:

    Programmable actuator’s stem extended, retracted or intermediate position on power failure.

    Supply voltage:

    24 VAC/VDC ±15%.
    Frequency 50/60 Hz ±3 Hz.

    Power consumption:

    Peak: < 6.6 VA (VAC); < 3.2 W (VDC)
    Operation: < 3.6 VA (VAC); < 1.8 W (VDC)
    Standby: < 1.6 VA (VAC); < 0.7 W (VDC)
    Peak consumption occurs for a short period after a power cut for recharging capacitors.

    Input signal:

    0(2)-10 VDC, Ri 47 kΩ.
    Adjustable hysteresis sensitivity 0.1-0.5 VDC.
    0.33 Hz low pass filter.
    Proportional:
    0-10, 10-0, 2-10 or 10-2 VDC.
    Proportional split-range:
    0-5, 5-0, 5-10 or 10-5 VDC.
    0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC.
    2-6, 6-2, 6-10 or 10-6 VDC.
    Proportional dual-range (for change-over):
    0-3.3 / 6.7-10 VDC,
    10-6.7 / 3.3-0 VDC,
    2-4.7 / 7.3-10 VDC or
    10-7.3 / 4.7-2 VDC.
    Default setting: Proportional 0-10 VDC.

    Output signal:

    0(2)-10 VDC, max. 8 mA, min. 1.25 kΩ.
    Ranges: See “Input signal”.
    Default setting: Proportional 0-10 VDC.

    Characteristics:

    Linear, EQM 0.25 and inverted EQM 0.25.
    Default setting: Linear.

    Control speed:

    4 or 6 s/mm.
    Default setting: 4 s/mm.

    Fail-safe delay:

    Adjustable between 0 and 10 seconds.
    Default setting: 2 s

    Power supply stabilisation delay:

    Adjustable between 1 and 5 seconds.
    Default setting: 2 s

    Pre-charging time:

    < 40 s

    Adjusting force:

    Push 500 N
    Pull 300 N

    Temperature:

    Media temperature: max. 120°C
    Operating environment: 0°C – +50°C (5-95%RH, non-condensing)
    Storage environment: -20°C – +50°C (5-95%RH, non-condensing)

    Ingress protection:

    IP54

    all directions

    (according to EN 60529)

    Protection class:

    (according to EN 61140)

    III (SELV)

    Cable:

    1, 2 or 5 m.
    Halogen free with wire end sleeves.
    Fire class B2ca – s1a, d1, a1 according to EN 50575.
    Type LiYY, 5x0.25 mm2.

    Relay cable (R24 version):
    1, 2 or 5 m.
    Halogen free with wire end sleeves.
    Fire class B2ca – s1a, d1, a1 according to EN 50575.
    Type LiYY, 3x0.34 mm2.

    Stroke:

    16,2 mm

    Automatic detection of the valve lift (stroke detection).

    Noise level:

    Max. 30 dBA

    Weight:

    I/O:
    0,23 kg, 1 m.
    0,27 kg, 2 m.
    0,40 kg, 5 m.
    R24:
    0,33 kg, 1 m.
    0,44 kg, 2 m.
    0,82 kg, 5 m.

    Connection to valve:

    Swivelling nut M30x1,5.

    Material:

    Cover: PC/ABS GF8
    Housing: PA GF40.
    Swivelling nut: Nickel-plated brass.

    Colour:

    White RAL 9016, grey RAL 7047.

    Marking:

    Label: IMI TA, CE, product name, article No. and technical specification.

    Certification CE:

    LV-D. 2014/35/EU: EN 60730-1, -2-14.
    EMC-D. 2014/30/EU: EN 60730-1, -2-14.
    RoHS-D. 2011/65/EU: EN 63000.

    Product standard:

    EN 60730

    Articles – TA-Slider 500 Fail-safe I/O

    TA-Slider 500 Fail-safe I/O

    Input signal: 0(2)-10 VDC

    With binary input, VDC output signal

    Cable length [m]
    Supply voltage
    EAN
    Article No
    With halogen free cable
    1
    24 VAC/VDC
    5902276898761
    322225-10614
    2
    24 VAC/VDC
    5902276898778
    322225-10615
    5
    24 VAC/VDC
    5902276898785
    322225-10616
    Articles – TA-Slider 500 Fail-safe R24

    TA-Slider 500 Fail-safe R24

    Input signal: 0(2)-10 VDC

    With binary input, VDC output signal and relay 24V

    Cable length [m]
    Supply voltage
    EAN
    Article No
    With halogen free cable
    1
    24 VAC/VDC
    5902276898792
    322225-10714
    2
    24 VAC/VDC
    5902276898808
    322225-10715
    5
    24 VAC/VDC
    5902276898815
    322225-10716
    Additional equipment

    For Bluetooth communication with the HyTune app, transfer configuration settings and manual override.

    TA-Dongle

    For Bluetooth communication with the HyTune app, transfer configuration settings and manual override.

    EAN
    Article No
    5901688828632
    322228-00001

    TA-Slider_500_F-S_R24_left_persp

    Select a format Download

    TA-Slider_500_F-S_I-O

    Select a format Download

    TA-Slider_500_F-S_I-O_right_persp

    Select a format Download

    TA-Slider_500_F-S_R24_right_persp

    Select a format Download

    TA-Slider_500_F-S_front

    Select a format Download

    TA-Slider_500_F-S_R24

    Select a format Download

    TA-Slider_500_F-S_I-O_left_persp

    Select a format Download