Features & Benefits
Adjustable set-point
Delivers desired differential pressure ensuring accurate balancing.
Shut-off function
Shut-off function makes maintenance easy and straightforward.
Measuring points
Simplifies the balancing procedure, and increases its accuracy.
Technical Information
Application:
Heating (not steam) and cooling systems.
Function:
Differential pressure control
Adjustable Δp
Measuring points
Shut-off
Dimensions:
2 1/2" - 4"
Pressure class:
Class 150
Temperature / Max. pressure:
-4 to 100 °F / 250 psi
200 °F / 235 psi
248 °F / 225 psi
Max. differential pressure (ΔpV):
117 ft H2O / 51 psi
Setting range:
6.69*-26.8 ft H2O / 2.90*-11.6 psi resp
13.4*-53.5 ft H2O / 5.80*-23.2 psi
*) Delivery setting
Temperature:
Max. working temperature: 248°F
Min. working temperature: 14°F
Media:
Water or neutral fluids, water-glycol mixtures (0-57%).
Material:
Valve body: Ductile iron EN-GJS-400-15 (~ASTM A536 Grade 60-40-18, ISO 1083 Grade 400-15)
Bonnet: AMETAL®
Cone: PTFE coated AMETAL®
Spindles: AMETAL®
O-rings: EDPM rubber
Seat seal: Plug with EPDM O-ring
Membrane: Reinforced EPDM rubber
Spring: Stainless steel
Handwheel: Polyamide
AMETAL® is the dezincification resistant alloy of IMI Hydronic Engineering.
Surface treatment:
Valve body: Epoxy painting.
Marking:
Body: TA, Class 150, DN, CE, ASTM 60-40-18, flow direction arrow and casting date (year, month, day).
Bonnet and handwheel: Label with STAP, DN, PN, ΔpL in ft H2O, psi and kPa, and bar code.
Face to face:
ISO 5752 series 1 and EN 558-1 series 1.
Flanges:
Class 150 according to ASME/ANSI B16.42 (~ PN 20 according to ISO 7005-2).
Articles
Flanged
3.28 ft (1 m) capillary pipe and transition nipple with shut-off are included.

Size | Number of bolt holes | D [in] | L [in] | H [in] | Cvm | qmax [gpm] | lb | EAN | Article No |
2.90-11.6 psi | |||||||||
2 1/2" | 4 | 7.1 | 11.4 | 12.6 | 41.8 | 112.2 | 47.4 | 7318793959607 | 52 266-065 |
3" | 4 | 7.5 | 12.2 | 13.3 | 63.8 | 171.2 | 52.9 | 7318793959706 | 52 266-080 |
4" | 8 | 9.1 | 13.8 | 13.8 | 127.6 | 342.3 | 63.9 | 7318793959805 | 52 266-090 |
5.80-23.2 psi | |||||||||
2 1/2" | 4 | 7.1 | 11.4 | 12.6 | 41.8 | 112.2 | 47.4 | 7318793958204 | 52 266-165 |
3" | 4 | 7.5 | 12.2 | 13.3 | 63.8 | 171.2 | 52.9 | 7318793958303 | 52 266-180 |
4" | 8 | 9.1 | 13.8 | 13.8 | 127.2 | 342.3 | 63.9 | 7318793958402 | 52 266-190 |
→ = Flow direction
Cvm = gpm at a pressure drop of 1 psi and maximum opening corresponding to the p-band (-25%).
Measuring point STAP

EAN | Article No |
7318793660602 | 52 265-205 |
Complete with connections for 6 mm pipe.
Extension kit for capillary pipe
Complete with connections for 6 mm pipe.

EAN | Article No | |
6 mm | 7318793781505 | 52 265-212 |
Capillary pipe

L | EAN | Article No |
3.28 ft (1 m) | 7318793661500 | 52 265-301 |
Capillary pipe connection with shut-off

EAN | Article No |
7318793781604 | 52 265-206 |
Venting
Plug
Venting

EAN | Article No |
7318793661609 | 52 265-302 |
For connection of capillary pipe while permitting simultaneous use of our balancing instrument.
Measuring point, two-way
For connection of capillary pipe while permitting simultaneous use of our balancing instrument.

EAN | Article No |
7318793784100 | 52 179-200 |
Images

52266065
Select a format Download
52266080
Select a format Download
STAP65persp_kat
Select a format Download
52266090
Select a format Download
52265302
Select a format Download
52265212
Select a format Download
52266190
Select a format Download
52266165
Select a format Download
52265206
Select a format Download
52266180
Select a format Download
STAP65
Select a format Download
52265205
Select a format Download
52265301
Select a format Download