Technical Information
Applications:
Heating water systems.
Deployment in systems according to EN 12828, SWKI HE301-01.
Functions:
Protection of the heat generator and the system from overheating in case of lack of water.
Pressure:
Min. admissible pressure, PSmin: 0 bar
Max. admissible pressure, PS: 10 bar
Temperature:
Max. admissible temperature, TS: 120 °C
Min. admissible temperature, TSmin: -10 °C
Material:
Main body made of nodular graphite iron, zinc coated.
Transportation and storage:
In frostless, dry places.
Approvals:
Component inspected TÜV-HWB-96.
Applications:
Heating, solar and cooling water systems.
Deployment in systems according to EN 12828, SWKI HE301-01.
Functions:
Control of the pre-pressure at expansion vessels. Auto on/off. Automatic calibration.
Pressure:
Min. admissible pressure, PSmin: 0 bar
Max. admissible pressure, PS: 10 bar
Temperature:
Max. admissible temperature, TS: 120 °C
Min. admissible temperature, TSmin: -10 °C
Material:
Rugged plastic housing.
Applications:
Heating, solar and cooling water systems.
Deployment in systems according to EN 12828, SWKI HE301-01.
Functions:
Control of the filling pressure at expansion vessels.
Pressure:
Min. admissible pressure, PSmin: 0 bar
Max. admissible pressure, PS: 4 bar
Temperature:
Max. admissible temperature, TS: 60 °C
Min. admissible temperature, TSmin: -10 °C
Applications:
Heating, solar and cooling water systems.
Deployment in systems according to EN 12828, SWKI HE301-01.
Functions:
Control of the filling pressure at expansion vessels.
Pressure:
Min. admissible pressure, PSmin: 0 bar
Max. admissible pressure, PS: 4 bar
Temperature:
Max. admissible temperature, TS: 120 °C
Min. admissible temperature, TSmin: -10 °C
Applications:
Heating, solar and cooling water systems.
Deployment in systems according to EN 12828, SWKI HE301-01.
Functions:
Shut-off of manometers. Pressure measurement only with pressed piston, otherwise the manometer is unpressurized.
Pressure:
Min. admissible pressure, PSmin: 0 bar
Max. admissible pressure, PS: 30 bar
Temperature:
Max. admissible temperature, TS: 100 °C
Min. admissible temperature, TSmin: -20 °C
Material:
Nickle-plated brass.
Applications:
Heating, solar and cooling water systems.
Deployment in systems according to EN 12828, SWKI HE301-01.
Functions:
Shut-off. Maintenance and disassembly of expansion vessels.
Pressure:
Min. admissible pressure, PSmin: 0 bar
Max. admissible pressure, PS: 16 bar
Temperature:
Max. admissible temperature, TS: 120 °C
Min. admissible temperature, TSmin: -10 °C
Media:
Non-aggressive and non-toxic system media.
Ethylene or propylene glycol-based antifreeze up to 50%.
Material:
Brass.
General:
Can only only be closed with the supplied allen key. Ball valve with DN 15 hose connection for fast draining.
Articles
No locking after turning off, change-over contact for signaling.2 welding connections.Vertical installation.
Low water protection WMS
No locking after turning off, change-over contact for signaling.
2 welding connections.
Vertical installation.
Type | H | L | m [kg] | U [V] | I [A] | EAN | Article No | |
10 bar (PS) | ||||||||
WMS 933.2 | 370 | 195 | 3,3 | 250 | 10 | 7640148638647 | 502 1004 |
Locking after turning off, change-over contact for signaling.2 welding connections.Vertical installation.
Low water protection WMS
Locking after turning off, change-over contact for signaling.
2 welding connections.
Vertical installation.
Type | H | L | m [kg] | U [V] | I [A] | EAN | Article No | |
10 bar (PS) | ||||||||
WMS 933.1 | 370 | 195 | 3,3 | 250 | 10 | 7640148638630 | 502 1003 |
Pre-pressure measuring gauge DME
Type | PS [bar] | m [kg] | EAN | Article No |
DME | 10 | 0,3 | 7640148638593 | 500 1048 |
Display range 0-4 bar, with green marking indicating working pressure range. Bottom connection.
Manometer H
Display range 0-4 bar, with green marking indicating working pressure range.
Bottom connection.
Type | PS [bar] | D | m [kg] | S | EAN | Article No |
H4 | 4 | 80 | 0,3 | R1/2 | 7640148638616 | 501 1037 |
Pressure display range 0-4 bar, temperature display range 0-120 °C, with marked green pressure bandwidth for working pressure. Rear connection.
Thermometer/Manometer TH
Pressure display range 0-4 bar, temperature display range 0-120 °C, with marked green pressure bandwidth for working pressure.
Rear connection.
Type | PS [bar] | D | m [kg] | S | EAN | Article No |
TH4 | 4 | 80 | 0,3 | R1/2 | 7640148638623 | 501 1038 |
Push button valve DH
Type | PS [bar] | m [kg] | S | EAN | Article No |
DH | 30 | 0,3 | G1/2 | 7640148638609 | 500 1060 |
Internal thread on both sides, screw connection on the vessel connection side.
Lock shield valve DLV
Internal thread on both sides, screw connection on the vessel connection side.
Type | PS [bar] | L | m [kg] | S | SG | SW | EAN | Article No |
DLV 15 | 16 | 114 | 0,53 | Rp3/4 | Rp1/2 | G3/4 | 7640148638562 | 535 1432 |
Female thread on both sides, flat sealing union for direct connection to all suitable expansion vessels.
Lock shield valve DLV
Female thread on both sides, flat sealing union for direct connection to all suitable expansion vessels.
Type | PS [bar] | L | m [kg] | S | SG | SW | EAN | Article No |
DLV 20 | 16 | 97 | 0,49 | Rp3/4 | G3/4 | G3/4 | 7640148638579 | 535 1434 |
DLV 25 | 16 | 100 | 0,54 | Rp1 | G1 | G3/4 | 7640148638586 | 535 1436 |
Internal thread on both sides, 90° bend with threaded seal for direct connection to Statico SU expansion vessels.
Connection set DLV A
Internal thread on both sides, 90° bend with threaded seal for direct connection to Statico SU expansion vessels.
Type | PS [bar] | L | m [kg] | S | SG | SW | EAN | Article No |
DLV 20 A | 16 | 130 | 0,61 | Rp3/4 | Rp3/4 | G3/4 | 7640148639842 | 746 2000 |
DLV 25 A | 16 | 138 | 0,71 | Rp1 | Rp1 | G3/4 | 7640161637214 | 301010-50601 |