Technical description – Low water protection

    Applications:

    Heating water systems.
    Deployment in systems according to EN 12828, SWKI HE301-01.

    Functions:

    Protection of the heat generator and the system from overheating in case of lack of water.

    Pressure:

    Min. admissible pressure, PSmin: 0 bar
    Max. admissible pressure, PS: 10 bar

    Temperature:

    Max. admissible temperature, TS: 120 °C
    Min. admissible temperature, TSmin: -10 °C

    Material:

    Main body made of nodular graphite iron, zinc coated.

    Transportation and storage:

    In frostless, dry places.

    Approvals:

    Component inspected TÜV-HWB-96.

    Technical description – Pre-pressure measuring gauge

    Applications:

    Heating, solar and cooling water systems.
    Deployment in systems according to EN 12828, SWKI HE301-01.

    Functions:

    Control of the pre-pressure at expansion vessels. Auto on/off. Automatic calibration.

    Pressure:

    Min. admissible pressure, PSmin: 0 bar
    Max. admissible pressure, PS: 10 bar

    Temperature:

    Max. admissible temperature, TS: 120 °C
    Min. admissible temperature, TSmin: -10 °C

    Material:

    Rugged plastic housing.

    Technical description – Manometer

    Applications:

    Heating, solar and cooling water systems.
    Deployment in systems according to EN 12828, SWKI HE301-01.

    Functions:

    Control of the filling pressure at expansion vessels.

    Pressure:

    Min. admissible pressure, PSmin: 0 bar
    Max. admissible pressure, PS: 4 bar

    Temperature:

    Max. admissible temperature, TS: 60 °C
    Min. admissible temperature, TSmin: -10 °C

    Technical description – Thermometer/Manometer

    Applications:

    Heating, solar and cooling water systems.
    Deployment in systems according to EN 12828, SWKI HE301-01.

    Functions:

    Control of the filling pressure at expansion vessels.

    Pressure:

    Min. admissible pressure, PSmin: 0 bar
    Max. admissible pressure, PS: 4 bar

    Temperature:

    Max. admissible temperature, TS: 120 °C
    Min. admissible temperature, TSmin: -10 °C

    Technical description – Push button valve

    Applications:

    Heating, solar and cooling water systems.
    Deployment in systems according to EN 12828, SWKI HE301-01.

    Functions:

    Shut-off of manometers. Pressure measurement only with pressed piston, otherwise the manometer is unpressurized.

    Pressure:

    Min. admissible pressure, PSmin: 0 bar
    Max. admissible pressure, PS: 30 bar

    Temperature:

    Max. admissible temperature, TS: 100 °C
    Min. admissible temperature, TSmin: -20 °C

    Material:

    Nickle-plated brass.

    Technical description – Lock shield valve

    Applications:

    Heating, solar and cooling water systems.
    Deployment in systems according to EN 12828, SWKI HE301-01.

    Functions:

    Shut-off. Maintenance and disassembly of expansion vessels.

    Pressure:

    Min. admissible pressure, PSmin: 0 bar
    Max. admissible pressure, PS: 16 bar

    Temperature:

    Max. admissible temperature, TS: 120 °C
    Min. admissible temperature, TSmin: -10 °C

    Media:

    Non-aggressive and non-toxic system media.
    Ethylene or propylene glycol-based antifreeze up to 50%.

    Material:

    Brass.

    General:

    Can only only be closed with the supplied allen key. Ball valve with DN 15 hose connection for fast draining.

    Low water protection

    No locking after turning off, change-over contact for signaling.2 welding connections.Vertical installation.

    Low water protection WMS

    No locking after turning off, change-over contact for signaling.
    2 welding connections.
    Vertical installation.

    Type
    H
    L
    m
    [kg]
    U
    [V]
    I
    [A]
    EAN
    Article No
    10 bar (PS)
    WMS 933.2
    370
    195
    3,3
    250
    10
    7640148638647
    502 1004

    Locking after turning off, change-over contact for signaling.2 welding connections.Vertical installation.

    Low water protection WMS

    Locking after turning off, change-over contact for signaling.
    2 welding connections.
    Vertical installation.

    Type
    H
    L
    m
    [kg]
    U
    [V]
    I
    [A]
    EAN
    Article No
    10 bar (PS)
    WMS 933.1
    370
    195
    3,3
    250
    10
    7640148638630
    502 1003
    Pre-pressure measuring gauge

    Pre-pressure measuring gauge DME

    Type
    PS
    [bar]
    m
    [kg]
    EAN
    Article No
    DME
    10
    0,3
    7640148638593
    500 1048
    Manometer

    Display range 0-4 bar, with green marking indicating working pressure range. Bottom connection.

    Manometer H

    Display range 0-4 bar, with green marking indicating working pressure range.
    Bottom connection.

    Type
    PS
    [bar]
    D
    m
    [kg]
    S
    EAN
    Article No
    H4
    4
    80
    0,3
    R1/2
    7640148638616
    501 1037
    Thermometer/Manometer

    Pressure display range 0-4 bar, temperature display range 0-120 °C, with marked green pressure bandwidth for working pressure. Rear connection.

    Thermometer/Manometer TH

    Pressure display range 0-4 bar, temperature display range 0-120 °C, with marked green pressure bandwidth for working pressure.
    Rear connection.

    Type
    PS
    [bar]
    D
    m
    [kg]
    S
    EAN
    Article No
    TH4
    4
    80
    0,3
    R1/2
    7640148638623
    501 1038
    Push button valve

    Push button valve DH

    Type
    PS
    [bar]
    m
    [kg]
    S
    EAN
    Article No
    DH
    30
    0,3
    G1/2
    7640148638609
    500 1060
    Lock shield valve

    Female thread on both sides, screw connection on the vessel connection side.

    Lock shield valve DLV

    Female thread on both sides, screw connection on the vessel connection side.

    Type
    PS
    [bar]
    L
    m
    [kg]
    S
    SG
    SW
    EAN
    Article No
    DLV 15
    16
    114
    0,53
    Rp3/4
    Rp1/2
    G3/4
    7640148638562
    535 1432

    Female thread on both sides, flat sealing union for direct connection to all suitable expansion vessels.

    Lock shield valve DLV

    Female thread on both sides, flat sealing union for direct connection to all suitable expansion vessels.

    Type
    PS
    [bar]
    L
    m
    [kg]
    S
    SG
    SW
    EAN
    Article No
    DLV 20
    16
    97
    0,49
    Rp3/4
    G3/4
    G3/4
    7640148638579
    535 1434
    DLV 25
    16
    100
    0,54
    Rp1
    G1
    G3/4
    7640148638586
    535 1436

    Female thread on both sides, 90° bend with threaded seal for direct connection to Statico SU expansion vessels.

    Connection set DLV A

    Female thread on both sides, 90° bend with threaded seal for direct connection to Statico SU expansion vessels.

    Type
    PS
    [bar]
    L
    m
    [kg]
    S
    SG
    SW
    EAN
    Article No
    DLV 20 A
    16
    130
    0,61
    Rp3/4
    Rp3/4
    G3/4
    7640148639842
    746 2000
    DLV 25 A
    16
    138
    0,71
    Rp1
    Rp1
    G3/4
    7640161637214
    301010-50601

    Low_water_protection_WMS_5021004

    Select a format Download

    5011037

    Select a format Download

    5001048

    Select a format Download

    Low_water_protection_WMS_5021003

    Select a format Download

    5011038

    Select a format Download

    5001060

    Select a format Download

    Safety_Devices_front

    Select a format Download

    DLV20-02

    Select a format Download

    Safety_valve_DLV_A_7462000

    Select a format Download

    DLV15-02

    Select a format Download

    DLV25-02

    Select a format Download