Features & Benefits
Convenient, reliable setup
Fully customisable by smartphone via Bluetooth using a TA-Dongle.
Fully configurable
More than 200 setup options allow input and output signals, binary input, relay, characteristics and many other parameters to be configured.
Easy diagnostics
Tracks the last 10 errors to allow system faults to be found quickly.
Quick copying of settings
Setup configuration can be copied quickly from the TA-Dongle to identical TA-Slider actuators.
Technical Information
Functions:
Proportional control
Manual override (TA-Dongle)
Stroke detection
Self-adjusting force
Mode, status and position indication
Stroke limitation setting
Minimum stroke setting
Valve blockage protection
Valve clogging detection
Error safe position
Diagnostic/Logging
Delayed start-up
BACnet/Modbus version:
+ 1 binary input, max. 100 Ω, cable max. 10 m or shielded.
+ 2 connections for Pt1000 temperature probe.
BACnet/Modbus CO (change-over) version:
+ 1 binary input, max. 100 Ω, cable max. 10 m or shielded.
+ 2 connections for Pt1000 temperature probe.
+ 1 relay, internally wired for control of TA-M106 actuator on TA-6-way valve (max. 2A, 30 VAC/VDC on resistive load).
Supply voltage:
24 VAC/VDC ±15%.
Frequency 50/60 Hz ±3 Hz.
BACnet/Modbus CO:
24 VAC only for enabling powering of TA-M106 actuator.
Power consumption:
BACnet/Modbus:
Operation: < 1.5 VA (VAC); < 1.0 W (VDC)
Standby: < 1.2 VA (VAC); < 0.75 W (VDC)
BACnet/Modbus CO:
Operation: < 1.5 VA (VAC)
Standby: < 1.2 VA (VAC)
TA-M106 actuator consumption must be added separately.
Input signal:
By BACnet/Modbus or with hybrid control mode;
0(2)-10 VDC, Ri 47 kΩ.
Adjustable hysteresis sensitivity 0.1-0.5 VDC.
0.33 Hz low pass filter.
Proportional:
0-10, 10-0, 2-10 or 10-2 VDC.
Proportional split-range:
0-5, 5-0, 5-10 or 10-5 VDC.
0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC.
2-6, 6-2, 6-10 or 10-6 VDC.
Proportional dual-range (for change-over):
0-3.3 / 6.7-10 VDC,
2-4.7 / 7.3-10 VDC,
0-4.5 / 5.5-10 VDC or
2-5.5 / 6.5-10 VDC.
Default setting: By BACnet/Modbus. If Hybrid mode chosen, default input signal is Proportional 0-10 VDC.
Output signal:
By BACnet/Modbus.
Characteristics:
Linear, EQM 0.25 and inverted EQM 0.25.
Default setting: Linear.
Control speed:
10 s/mm
Adjusting force:
160/200 N
Self-adjusting for IMI Hydronic Engineering valves.
Temperature:
Media temperature: max. 120°C
Operating environment: 0°C – +50°C (5-95%RH, non-condensing)
Storage environment: -20°C – +70°C (5-95%RH, non-condensing)
Ingress protection:
IP54
all directions
(according to EN 60529)
Protection class:
(according to EN 61140)
III (SELV)
Cables:
Separate overmoulded cables (see Additional equipment).
Type LiYCY 5x0.34 mm2 (cables A and B) and type LiYY 6x0.34 mm2 (cable C).
Halogen free, fire class B2ca – s1a, d1, a1 according to EN 50575.
Relay cable (CO version):
Type LiYY 3x0.34 mm2.
1, 2 or 5 m. With connector to actuator TA-M106.
Halogen free, fire class B2ca – s1a, d1, a1 according to EN 50575.
Stroke:
6,9 mm
Automatic detection of the valve lift (stroke detection).
Noise level:
Max. 30 dBA
Weight:
BACnet/Modbus: 0.22 kg
BACnet/Modbus CO:
0.26 kg, 1 m relay cable.
0.31 kg, 2 m relay cable.
0.45 kg, 5 m relay cable.
Connection to valve:
Swivelling nut M30x1,5.
Material:
Cover: PC/ABS GF8
Housing: PA GF40.
Swivelling nut: Nickel-plated brass.
Colour:
White RAL 9016, grey RAL 7047.
Marking:
Label: IMI TA, CE, product name, article No. and technical specification.
Certification CE:
LV-D. 2014/35/EU: EN 60730-1, -2-14.
EMC-D. 2014/30/EU: EN 60730-1, -2-14.
RoHS-D. 2011/65/EU: EN 63000.
Product standard:
EN 60730
Articles
TA-Slider 160 BACnet/Modbus
Input signal: Via Bus or 0(2)-10 VDC
With binary input and 2 connections for Pt1000 temperature probe
Bus | EAN | Article No |
BACnet | 5901688823590 | 322224-13011 |
Modbus | 5901688823538 | 322224-12011 |
TA-Slider 160 BACnet/Modbus CO
Input signal: Via Bus or 0(2)-10 VDC
With binary input, 2 connections for Pt1000 temperature probe and relay 24V
Relay cable length [m] | Bus | EAN | Article No | |
With halogen free relay cable | ||||
1 | BACnet CO | 5901688823743 | 322224-13514 | |
2 | BACnet CO | 5902276896743 | 322224-13515 | |
5 | BACnet CO | 5901688823767 | 322224-13516 | |
1 | Modbus CO | 5901688823682 | 322224-12514 | |
2 | Modbus CO | 5901688823699 | 322224-12515 | |
5 | Modbus CO | 5901688823705 | 322224-12516 |
For Bluetooth communication with the HyTune app, transfer configuration settings and manual override.
TA-Dongle
For Bluetooth communication with the HyTune app, transfer configuration settings and manual override.
EAN | Article No |
5901688828632 | 322228-00001 |
A: To connect the first TA-Slider 160/500 BACnet or Modbus of a daisy chain to the Bus.B: Between two actuators in a daisy chain.C: To enable hybrid mode or provide power supply if the daisy chain is long.
Daisy chain cables
A: To connect the first TA-Slider 160/500 BACnet or Modbus of a daisy chain to the Bus.
B: Between two actuators in a daisy chain.
C: To enable hybrid mode or provide power supply if the daisy chain is long.
Cable length [m] | EAN | Article No | |
Halogen free cable | |||
Type A | |||
1,5 | 5902276898228 | 322042-80012 | |
5 | 5902276898235 | 322042-80013 | |
10 | 5902276898242 | 322042-80014 | |
Type B | |||
1,5 | 5902276898259 | 322042-80015 | |
5 | 5902276898266 | 322042-80016 | |
10 | 5902276898273 | 322042-80017 | |
Type C | |||
1,5 | 5902276898280 | 322042-80018 | |
5 | 5902276898297 | 322042-80019 | |
10 | 5902276898303 | 322042-80020 |