Technical description

    Application:

    Domestic hot water systems in private houses, blocks of flats, hospitals, old-age and nursing homes, hotels, shower-rooms of sports facilities, industrial and commercial buildings.

    Function:

    The TA-MATIC is intended mainly as a central mixing unit for domestic hot water systems in apartment buildings, in systems with or without hot water circulation.
    It works most efficient, if the system is equipped with a circulation pump. In this case, the unit can also be used as a central mixer for shower and bath facilities.

    Dimensions:

    DN 65-80

    Pressure class:

    PN 10

    Temperature:

    Max. working temperature:90°C

    Temperature range:

    Standard temperature settings:
    DN 65: 25°C or 55°C
    DN 80: 55°C
    Factory-set standard temperatures can be adjusted within the limits:
    25°C: 20-30°C
    55°C: 45-65°C

    Material:

    Valve body: Gunmetal CC499K (CuSn5Zn5Pb2-C)
    Seat: Stainless steel
    Expansion medium in the thermostat sensing element are gaseous hydrocarbon, wax and pulverized copper.

    Marking:

    TA-MATIC 3410, JRGUMAT, PN10 and dimension.

    Connection:

    Flanges according to EN 1092-2.

    Packaging:

    The packaging of the TA-MATIC can be used to provide insulation against heat losses.

    Articles

    Excl. flange gaskets.

    TA-MATIC 3410

    Excl. flange gaskets.

    No. of bolt holes:
    DN 65: 4
    DN 80: 8

    DN
    °C*
    °C**
    d1
    d2
    L1
    L2
    L3
    H1
    H2
    Kg
    EAN
    Article No
    65
    25
    20-30
    185
    G1 1/2
    145
    290
    112
    82
    121
    23
    7613263014399
    52 742-565
    65
    55
    45-65
    185
    G1 1/2
    145
    290
    112
    82
    121
    23
    7613263014375
    52 745-565
    80
    55
    45-65
    200
    G2
    155
    310
    124
    92
    127
    28
    7613263014313
    52 745-580

    *) Standard mixing temperature
    **) Adjustable range
    ***) Minimum clearance 100 mm

    Accessories

    for closing the circulation connection when no circulation is used. With gasket. Brass.

    Cap

    for closing the circulation connection when no circulation is used.
    With gasket. Brass.

    d2
    Valve DN
    EAN
    Article No
    G1 1/2
    DN 65
    7613263014245
    83 255-600
    G2
    DN 80
    7613263014238
    83 256-400

    83255600

    Select a format Download

    TA-Matic_3410_kat

    Select a format Download

    TA-Matic_3410

    Select a format Download

    Technical specifications

    Drawings