Features & Benefits

    Higher Efficiency Cyclonic vacuum degassing

    Significantly higher efficiency than most other vacuum degassing systems.

    Direct degassing of make-up water

    For additional protection against corrosion.

    Easy Commissioning, Remote Access and Trouble-shooting

    Integrated standard connections to our IMI Webserver and to BMS.

    Vento Compact

    Compact design for floor and wall hanging installation

    Optional sound absorbing wall bracket

    For Vento Compact in installations particularly sensitive to structure-borne sound.

    Technical description – Control unit TecBox

    Applications:

    Heating, solar and chilled water systems. For systems according to EN 12828, SWKI HE301-01, EN 12976, ENV 12977, EN 12952, EN 12953

    Media:

    Non-aggressive and non-toxic system media.
    Addition of antifreeze agent up to 50%.

    Pressure:

    Min. admissible pressure, PSmin: -1 bar
    Max. admissible pressure, PS: see Articles

    Temperature:

    Min. admissible temperature, TSmin: 0°C
    Max. admissible temperature, TS: 90°C

    Max. admissible ambient temperature, TA: 40°C
    Min. admissible ambient temperature, TAmin: 0°C

    Supply voltage:

    Vento V/VF:
    1 x 230 V (± 10 %) / 50 Hz

    Vento VI:
    Main voltage: 3x400V (± 10%) / 50Hz (3P+PE)
    Control voltage: 230V (± 10%) / 50Hz (P+N+PE)

    Electrical connections:

    Onsite fuses according to power demand and local norms
    3 potential free outputs (NO) for external alarm indication (230V max. 2A)
    1 RS 485 In/Output
    1 Ethernet RJ45 plug socket
    1 USB Hub plug socket

    Terminal strip in PowerCube for direct wiring (Vento VI).

    Enclosure class:

    IP54 according to EN 60529

    Mechanical connections:

    Vento V/VI:
    Sin1: inlet from the system G3/4"
    Sout: outlet to the system G3/4"
    Swm: inlet water make-up G3/4"
    Vento VF:
    Sin1: inlet from the system G1/2"
    Sout: outlet to the system G1/2"
    Swm: inlet water make-up G3/4"

    Material:

    Metal components with medium contact: carbon steel, cast iron, stainless steel, AMETAL®, brass, gun metal.

    Transportation and storing:

    In frostless, dry places.

    Standard:

    Constructed according to
    LV-D. 2014/35/EU
    EMC-D. 2014/30/EU

    Control unit TecBox, Vento Compact Connect Heating

    Vento Compact Connect

    Cyclonic vacuum degassing unit. 1 pump and 2 solenoid valves, cyclonic vacuum degassing unit, connection for water make-up with solenoid valve and water meter and BrainCube Connect control.
    2 connection hoses with ball valves. Connections G1/2”.

    Type
    B
    H
    T
    m
    [kg]
    Pel
    [kW]
    VNd
    [m3]
    SPL
    [dB(A)]
    dpu
    [bar]
    EAN
    Article No
    10 bar (PS)
    V 2.1 FE
    520
    575
    350
    30
    0,75
    10
    ~55*
    0,5 - 2,5
    7640161642294
    303030-20400

    T = Depth of the device

    VNd = Water capacity for which a device is rated

    Pel = Electric load

    dpu = Working pressure range

    *) Pump operation

    Sound absorbing wall bracket for Vento VS/VF Connect

    Wall bracket WB VSF

    Sound-absorbing wall bracket for Simply Vento Connect and Vento Compact Connect.
    Reliably reduces the transmission of structure-borne sound from the unit to the mounting wall to a minimum.

    Type
    B
    H
    T
    m
    [kg]
    EAN
    V 2.1 S
    376
    500
    520
    7,5
    7640161644557
    303032-30021

    B = Centre-to-centre distance for optimum mounting

    Control unit TecBox, Vento Connect Heating

    Vento V/VI .1 E Connect

    Cyclonic vacuum degassing unit. 1 pump, 2 solenoid valves (Vento V), 1 solenoid valve and 1 motor driven valve (Vento VI), 1 cyclonic vacuum degassing unit, connection for water make-up with solenoid valve and water meter, and BrainCube Connect control.

    Type
    B
    H
    T
    m
    [kg]
    Pel
    [kW]
    VNd
    [m3]
    SPL
    [dB(A)]
    dpu
    [bar]
    EAN
    Article No
    10 bar (PS)
    V 4.1 E
    500
    920
    530
    38
    0,75
    300
    ~55*
    1-2,5
    7640161629752
    812 1101
    V 6.1 E
    500
    920
    530
    40
    1,1
    300
    ~55*
    1,5-3,5
    7640161629769
    812 1102
    V 8.1 E
    500
    920
    530
    41
    1,4
    300
    ~55*
    2-4,5
    7640161629776
    812 1103
    V 10.1 E
    500
    1300
    530
    57
    1,7
    300
    ~60*
    3,5-6,5
    7640161629783
    812 1104
    13 bar (PS)
    V 14.1 E
    500
    1300
    530
    67
    1,7
    300
    ~60*
    5,5-10
    7640161629790
    812 1105
    16 bar (PS)
    VI 19.1 E
    570
    1086
    601
    78
    2,6
    300
    ~60*
    6,5-15,5
    7640161636774
    303031-60600
    25 bar (PS)
    VI 25.1 E
    570
    1258
    601
    85
    3,4
    300
    ~60*
    10,5-20,5
    7640161636781
    303031-60700

    T = Depth of the device

    VNd = Water capacity for which a device is rated

    Pel = Electric load

    dpu = Working pressure range

    *) Pump operation

    Control unit TecBox, Vento Connect Cooling

    Vento V/VI .1 EC Connect

    Cyclonic vacuum degassing unit. 1 pump and 2 solenoid valves (Vento V), 1 solenoid valve and 1 motor driven valve (Vento VI), 1 cyclonic vacuum degassing unit, connection for water make-up with solenoid valve and water meter, and BrainCube Connect control.

    Cooling insulation with condensation water protection.

    Type
    B
    H
    T
    m
    [kg]
    Pel
    [kW]
    VNd
    [m3]
    SPL
    [dB(A)]
    dpu
    [bar]
    EAN
    Article No
    10 bar (PS)
    V 4.1 EC
    500
    920
    530
    39
    0,75
    300
    ~55*
    1-2,5
    7640161629806
    812 1201
    V 6.1 EC
    500
    920
    530
    41
    1,1
    300
    ~55*
    1,5-3,5
    7640161629813
    812 1202
    V 8.1 EC
    500
    920
    530
    42
    1,4
    300
    ~55*
    2-4,5
    7640161629820
    812 1203
    V 10.1 EC
    500
    1300
    530
    58
    1,7
    300
    ~60*
    3,5-6,5
    7640161629837
    812 1204
    13 bar (PS)
    V 14.1 EC
    500
    1300
    530
    68
    1,7
    300
    ~60*
    5,5-10
    7640161629844
    812 1205
    16 bar (PS)
    VI 19.1 EC
    570
    1086
    601
    86
    2,6
    300
    ~60*
    6,5-15,5
    7640161636958
    303031-70600
    25 bar (PS)
    VI 25.1 EC
    570
    1258
    601
    94
    3,4
    300
    ~60*
    10,5-20,5
    7640161636941
    303031-70700

    T = Depth of the device

    VNd = Water capacity for which a device is rated

    Pel = Electric load

    dpu = Working pressure range

    *) Pump operation

    Pleno P water make-up module for Vento V/VI/VF

    Hydraulic unit for water make up operation with Vento/Transfero Connect. Consists of Pleno P BA4 R back flow preventer and Pleno P AB5 modules, with protection class 5 according to EN 1717.

    Pleno P AB5 R

    Hydraulic unit for water make up operation with Vento/Transfero Connect. Consists of Pleno P BA4 R back flow preventer and Pleno P AB5 modules, with protection class 5 according to EN 1717.

    Type
    PS
    [bar]
    T
    H1
    H2
    m
    [kg]
    qwm
    [l/h]
    EAN
    Article No
    AB5 R
    10
    220
    280
    1000
    3,8
    250
    7640161630161
    813 3330

    qwm = maximum water make-up volume

    T = Depth of the device

    Hydraulic unit for water make-up operation with Vento/Transfero Connect, Pleno PX/PIX, Simply Compresso C 2.1-80 SWM, and in combination with Pleno Refill modules. Features a shut off valve, check valve, filter and a type BA backflow preventer (protection class 4) according to EN 1717.Connection (Swm): G1/2

    Pleno P BA4 R

    Hydraulic unit for water make-up operation with Vento/Transfero Connect, Pleno PX/PIX, Simply Compresso C 2.1-80 SWM, and in combination with Pleno Refill modules. Features a shut off valve, check valve, filter and a type BA backflow preventer (protection class 4) according to EN 1717.
    Connection (Swm): G1/2

    Type
    PS
    [bar]
    B
    L
    H
    m
    [kg]
    qwm
    [l/h]
    EAN
    Article No
    BA4 R
    10
    210
    1300
    135
    1,1
    350*
    250**
    50***
    q(pw-pout) ****
    7640161630147
    813 3310

    qwm = make-up water flow
    *) Maximum average for make-up water degassing with Vento V/VI and Transfero TV/TVI
    **) Maximum average for make-up water degassing with Vento Compact
    ***) when using flow limiter for operation with low-flow water treatment cartridges
    **** when used in combination with Pleno PX/PIX, see q(pw-pout) diagram in Pleno Connect datasheet

    Pleno P water make-up modules for Vento V/VI

    Hydraulic unit for water make up operation with Vento/Transfero Connect. Consists of Pleno P BA4 R back flow preventer and Pleno P AB5 modules, with protection class 5 according to EN 1717.

    Pleno P AB5 R

    Hydraulic unit for water make up operation with Vento/Transfero Connect. Consists of Pleno P BA4 R back flow preventer and Pleno P AB5 modules, with protection class 5 according to EN 1717.

    Type
    PS
    [bar]
    T
    H1
    H2
    m
    [kg]
    qwm
    [l/h]
    EAN
    Article No
    AB5 R
    10
    220
    280
    1000
    3,8
    250
    7640161630161
    813 3330

    qwm = make-up water flow

    T = Depth of the device

    Hydraulic unit for water make up operation with Vento/Transfero Connect. Consists of a breaktank type AB (protection class 5) according EN 1717. For installation on the back of each unit. Can be used for 3rd party softening modules which do not fulfil the requirement of qwm min 1300 l/h and therefore can't be directly connected.

    Pleno P AB5

    Hydraulic unit for water make up operation with Vento/Transfero Connect. Consists of a breaktank type AB (protection class 5) according EN 1717. For installation on the back of each unit. Can be used for 3rd party softening modules which do not fulfil the requirement of qwm min 1300 l/h and therefore can't be directly connected.

    Type
    PS
    [bar]
    T
    H1
    H2
    m
    [kg]
    qwm
    [l/h]
    EAN
    Article No
    AB5
    10
    220
    280
    1000
    1,83
    250
    7640161630154
    813 3320

    qwm = make-up water flow

    T = Depth of the device