Features & Benefits

    BrainCube control

    Self-optimising with memory function.

    Easy commissioning, remote access and remote support during troubleshooting Built-in interfaces for communication with the IMI web server and ModBus TCP and RTU for building control applications.

    Pressurization

    2 pumps, 2 spill connections each with 2 in series connected spill valves. Switching is time and load dependent.

    PowerCube switch cabinet with halogen-free wiring

    main switch with emergency stop function; 2 motor circuit breakers; Automatic soft start and soft stop for each pump.

    Fillsafe water make-up monitoring

    With the possibility to control water make-up through a Pleno PX.

    Technical description – Control unit TecBox

    Applications:

    Heating, solar and chilled water systems.
    For systems to EN 12828 and optional >110 °C to EN 12952, EN 12953 with additional pressure limiters Paz PMIN and water level limiter ComCube DML Connect, solar systems according to EN 12976, ENV 12977 with on-site overtemperature protection in the event of power failure.

    Media:

    According to VDI 2035 for non-aggressive and non-toxic system media.
    Addition of antifreeze agent up to 50%.

    Pressure:

    Min. admissible pressure, PSmin: 0 bar
    Max. admissible pressure, PS: see Articles

    Temperature:

    Max. admissible temperature, TS: 90°C
    Min. admissible temperature, TSmin: 0°C
    Max. admissible ambient temperature, TA: 40°C
    Min. admissible ambient temperature, TAmin: 5°C

    Accuracy:

    Precision pressure maintenance ±0,2 bar.

    Supply voltage:

    Main current: 3x 400V / 50Hz (3P + PE)
    Control voltage: 230V / 50Hz (P + N + PE)

    Electrical connections:

    Onsite fuses according to power demand and local norms.
    4 potential free outputs ((individual parameterizable) for external message display (230V max. 2A),
    2 potential-free outputs for status messages,
    Motor circuit breakers of pump P1 and P2,
    1 potential-free output for controlling an external water make-up device,
    3 Grinding terminals for e.B. for optional pressure-, level-, temperature limiter.
    1 RS 485 In/Output,
    1 Ethernet RJ45 plug socket,
    Terminal strip in PowerCube for direct wiring of the above-mentioned connectors,
    1 USB Hub plug socket,
    Software upgrade and LOG File Download.

    Fire protection:

    Complete electrical cabling in halogen-free version according to EN 50575 and EN 13501-6. Classification Cca s1-d1-a1 for external cables. Classification Dca s2-d2-a2 for single wires within the PowerCube control cabinet.

    Enclosure class:

    IP 54

    Material:

    In essence: steel, brass and bronze

    Connections:

    Water make-up (Swm): Rp3/4
    Connection vessel (Sv): 80/6 DN/PN

    Standard:

    Constructed according to

    MD 2006/42/EC, Annex II 1.A
    EMC-D. 2014/30/EU

    Technical description – Expansion vessels

    Applications:

    Only together with Control unit TecBox.
    See Applications under Technical description - Control unit TecBox.

    Transfero TGIH:

    With additional electronic measuring foot LT and connection possibility of a ComCube DML for individual content measurement, content display and alarm circuit for Min/Max water level. Recommended for applications according to EN 12952 and EN 12953.

    Media:

    According to VDI 2035 for non-aggressive and non-toxic system media.
    Addition of antifreeze agent up to 50%.

    Pressure:

    Min. admissible pressure, PSmin: 0 bar
    Max. admissible pressure, PS: 2 bar

    Temperature:

    Max. admissible temperature, TS: 120 °C
    Min. admissible temperature, TSmin: -10 °C
    Max. admissible bag temperature, TB: 70 °C
    Min. admissible bag temperature, TBmin: 5 °C

    Material:

    Steel, welded. Color beryllium.

    Standard:

    Constructed according to PED 2014/68/EU.

    Warranty:

    5-year warranty for the vessel.
    5-year warranty for the airproof butyl bag.

    Control unit TecBox

    Connection vessel (Sv): DN 80 / PN 6Connection water make-up (SWM): Rp 3/4

    Transfero TI Connect

    Connection vessel (Sv): DN 80 / PN 6
    Connection water make-up (SWM): Rp 3/4

    Type*
    PS
    [bar]
    H
    m
    [kg]
    Sout
    [DN/PN]
    Pel
    [kW]
    SPL
    [dB(A)]
    EAN
    Article No
    TI 90.2 PC1
    16
    1200
    135
    50/40
    3,0
    <70
    7640161643017
    301030-80912
    TI 120.2 PC1
    16
    1200
    145
    50/40
    3,8
    <70
    7640161643024
    301030-80913
    TI 150.2 PC1
    16
    1200
    170
    50/40
    5,4
    <70
    7640161643031
    301030-80914
    TI 190.2 PC1
    25
    1200
    195
    50/40
    5,4
    <70
    7640161643038
    301030-80915
    TI 230.2 PC1
    25
    1300
    215
    50/40
    7,2
    <70
    7640161643055
    301030-80916
    TI 61.2 PC1
    10
    1200
    135
    80/16
    3,0
    <70
    7640161643062
    301030-81111
    TI 91.2 PC1
    10
    1200
    150
    80/16
    4,2
    <70
    7640161643079
    301030-81112
    TI 111.2 PC1
    16
    1200
    175
    80/16
    5,4
    <70
    7640161643086
    301030-81113
    TI 161.2 PC1
    16
    1300
    190
    80/16
    7,2
    <70
    7640161643093
    301030-81114
    TI 231.2 PC1
    25
    1600
    250
    80/40
    12,4
    <70
    7640161643116
    301030-81116
    TI 62.2 PC1
    10
    1200
    185
    80/16
    5,4
    <70
    7640161643123
    301030-81117
    TI 102.2 PC1
    16
    1200
    205
    80/16
    7,2
    <70
    7640161643130
    301030-81118
    TI 132.2 PC1
    16
    1200
    215
    80/16
    9,4
    <70
    7640161643147
    301030-81119
    TI 182.2 PC1
    25
    1400
    280
    80/40
    12,4
    <70
    7640161643154
    301030-81120

    *) Constructions ≥ TI ..3.2 and special installations upon request.

    Accessories for control modules: Communication module.
    Additional equipment: Pressure limiter Paz PMIN and water level indicator ComCube DML.
    Master-Slave.

    Accessories for control modules

    Display of the content of the connected expansion vessel. 4 potential-free, individually parametric digital outputs (NO). Each digital output is individually electronically invertible (NC). 3.5" TFT color touchscreen with lighting.Integrated standard connections (Ethernet, RS 485) to the IMI web server and the design control technology (Modbus).

    ComCube DML Connect

    Display of the content of the connected expansion vessel. 4 potential-free, individually parametric digital outputs (NO). Each digital output is individually electronically invertible (NC).
    3.5" TFT color touchscreen with lighting.
    Integrated standard connections (Ethernet, RS 485) to the IMI web server and the design control technology (Modbus).

    Type
    B
    H
    T
    m
    [kg]
    Pel
    [kW]
    EAN
    Article No
    DML Connect
    180
    220
    140
    1,0
    0,1
    7640161643168
    301032-30018

    T = Depth of the device

    Communicator. Factory assembly in Transfero TI.2 galvanically isolated analoge outputs 4-20 mA for connection to BMS, isolation voltage 2.5 kVAC. Completely wired to mounting rail in the PowerCube control cabinet.

    ComCube DCA TI

    Communicator. Factory assembly in Transfero TI.


    2 galvanically isolated analoge outputs 4-20 mA for connection to BMS, isolation voltage 2.5 kVAC. Completely wired to mounting rail in the PowerCube control cabinet.

    Type
    B
    H
    T
    m
    [kg]
    Pel
    [kW]
    EAN
    Article No
    DCA TI
    17,5
    120
    146
    0,2
    0,1
    7640148638746
    814 1015

    T = Depth of the device

    Expansion vessels

    Primary vessel. 1 electr. measuring foot for content measurement, 1 electr. measuring foot for additional water level indication and min/max alarms.

    Transfero TGI...H

    Primary vessel. 1 electr. measuring foot for content measurement, 1 electr. measuring foot for additional water level indication and min/max alarms.

    Type*
    VN
    [l]
    D
    H
    H***
    m
    [kg]
    S
    Sw
    EAN
    Article No
    2 bar (PS)
    TGI 1000H
    1000
    850
    2199
    2210
    285
    G1 1/2
    G3/4
    7640148632102
    713 3200
    TGI 1500H
    1500
    1016
    2351
    2381
    365
    G1 1/2
    G3/4
    7640148632119
    713 3201
    TGI 2000H
    2000
    1016
    2848
    2876
    645
    G1 1/2
    G3/4
    7640148632126
    713 3206
    TGI 3000H
    3000
    1300
    2951
    3016
    805
    G1 1/2
    G3/4
    7640148632133
    713 3203
    TGI 4000H
    4000
    1300
    3592
    3633
    915
    G1 1/2
    G3/4
    7640148632140
    713 3204
    TGI 5000H
    5000
    1300
    4216
    4275
    1015
    G1 1/2
    G3/4
    7640148632157
    713 3205

    VN = Nominal volume

    *) Special vessel upon request.

    **) Tolerance 0 /-100.

    ***) Max. height when vessel is tilted. Tolerance 0 /-100.

    Additional equipment: Pressure limiter Paz PMIN and water level limiter DML Connect.

    Secondary vessel.

    Transfero TGI...E

    Secondary vessel.

    Type*
    VN
    [l]
    D
    H
    H***
    m
    [kg]
    S
    Sw
    EAN
    Article No
    2 bar (PS)
    TGI 1000E
    1000
    850
    2199
    2210
    280
    G1 1/2
    G3/4
    7640148632041
    713 3300
    TGI 1500E
    1500
    1016
    2351
    2381
    360
    G1 1/2
    G3/4
    7640148632058
    713 3301
    TGI 2000E
    2000
    1016
    2848
    2876
    640
    G1 1/2
    G3/4
    7640148632065
    713 3306
    TGI 3000E
    3000
    1300
    2951
    3016
    800
    G1 1/2
    G3/4
    7640148632072
    713 3303
    TGI 4000E
    4000
    1300
    3592
    3633
    910
    G1 1/2
    G3/4
    7640148632089
    713 3304
    TGI 5000E
    5000
    1300
    4216
    4275
    1010
    G1 1/2
    G3/4
    7640148632096
    713 3305

    VN = Nominal volume

    *) Special vessel upon request.

    **) Tolerance 0 /-100.

    ***) Max. height when vessel is tilted. Tolerance 0 /-100.

    Additional equipment: Pressure limiter Paz PMIN and water level limiter DML Connect.

    Primary vessel. Measuring foot for content measurement.

    Transfero TGI

    Primary vessel. Measuring foot for content measurement.

    Type*
    VN
    [l]
    D
    H
    H***
    m
    [kg]
    S
    Sw
    EAN
    Article No
    2 bar (PS)
    TGI 1000
    1000
    850
    2199
    2210
    280
    G1 1/2
    G3/4
    7640148631983
    713 3100
    TGI 1500
    1500
    1016
    2351
    2381
    360
    G1 1/2
    G3/4
    7640148631990
    713 3101
    TGI 2000
    2000
    1016
    2848
    2876
    640
    G1 1/2
    G3/4
    7640148632003
    713 3106
    TGI 3000
    3000
    1300
    2951
    3016
    800
    G1 1/2
    G3/4
    7640148632010
    713 3103
    TGI 4000
    4000
    1300
    3592
    3633
    910
    G1 1/2
    G3/4
    7640148632027
    713 3104
    TGI 5000
    5000
    1300
    4216
    4275
    1010
    G1 1/2
    G3/4
    7640148632034
    713 3105

    VN = Nominal volume

    *) Special vessel upon request.

    **) Tolerance 0 /-100.

    ***) Max. height when vessel is tilted. Tolerance 0 /-100.

    Additional equipment: Pressure limiter Paz PMIN and water level limiter DML Connect.

    Control unit TecBox, Pleno PX

    Hydraulic unit for water make-up operation with Compresso Connect. Water make-up without pumps. 1 solenoid valve, 1 electronic water meter, connection for Pleno P BA4 R.Connection in (Swm): G3/4.Connection out (Sout): G1/2.

    Pleno PX

    Hydraulic unit for water make-up operation with Compresso Connect. Water make-up without pumps. 1 solenoid valve, 1 electronic water meter, connection for Pleno P BA4 R.
    Connection in (Swm): G3/4.
    Connection out (Sout): G1/2.

    Type
    PS
    [bar]
    B
    H
    T
    m
    [kg]
    Pel
    [kW]
    Kvs
    EAN
    Article No
    PX
    10
    198
    356
    150
    1,5
    0,02
    1,4
    7640161641792
    301060-10011

    T = Depth of the device

    Pel = Electric load

    Water make-up unit Pleno PX - 25 with 1" connection on request.

    Pleno Refill 16000, 36000, 48000 / Pleno Refill Demin 13500, 18000

    Softening unit

    3/4" swivelling nut, 3/4" external thread suitable for flat gasket.
    Nominal pressure: PS 8
    Max. working temperature: 45°C
    Min. working temperature: > 4°C

    Type
    Capacity
    l x °dH
    Sin
    Sout
    D
    H
    L
    m
    [kg]
    EAN
    Article No
    Refill 16000
    16000
    G3/4
    G3/4
    195
    383
    455
    9,1
    7640161630475
    813 3210
    Refill 36000
    36000
    G3/4
    G3/4
    220
    466
    455
    13
    7640161630482
    813 3220
    Refill 48000
    48000
    G3/4
    G3/4
    270
    458
    455
    16,2
    7640161630499
    813 3230

    → = Flow direction

    Demineralisation unit

    3/4" swivelling nut, 3/4" external thread suitable for flat gasket.
    Nominal pressure: PS 8
    Max. working temperature: 45°C
    Min. working temperature: > 4°C

    Type
    Capacity
    l x °dH
    Sin
    Sout
    D
    H
    L
    m
    [kg]
    EAN
    Article No
    Refill Demin 13500
    13500
    G3/4
    G3/4
    220
    466
    455
    13
    7640161630505
    813 3260
    Refill Demin 18000
    18000
    G3/4
    G3/4
    270
    458
    455
    16,2
    7640161630512
    813 3270

    → = Flow direction

    Water make-up protection module

    Hydraulic unit for water make-up operation with Vento/Transfero Connect, Pleno PX/PIX, Simply Compresso C 2.1-80 SWM, and in combination with Pleno Refill modules. Features a shut off valve, check valve, filter and a type BA backflow preventer (protection class 4) according to EN 1717.Connection (Swm): G1/2

    Pleno P BA4 R

    Hydraulic unit for water make-up operation with Vento/Transfero Connect, Pleno PX/PIX, Simply Compresso C 2.1-80 SWM, and in combination with Pleno Refill modules. Features a shut off valve, check valve, filter and a type BA backflow preventer (protection class 4) according to EN 1717.
    Connection (Swm): G1/2

    Type
    PS
    [bar]
    W
    L
    H
    m
    [kg]
    qwm
    [l/h]
    EAN
    Article No
    BA4 R
    10
    210
    1300
    135
    1,1
    350*
    250**
    50***
    q(pw-pout) ****
    7640161630147
    813 3310

    qwm = make-up water flow

    * maximum average value for make-up water degassing with Vento V/VI and Transfero TV/TVI
    ** maximum average value for make-up water degassing with Vento Compact
    *** when using flow limiter for operation with low flow water treatment cartridges
    **** for combination with Pleno PX/PIX see q(pw-pout) diagram in Pleno Connect datasheet

    T = Depth of the device

    Additional equipment

    Minimum pressure switch. For retrofitting to Transfero TI.Fitting on site into TecBox and connection to control module.TÜV-tested in accordance with VdTÜV Druck 100/1 for specialised equipment and according to PED 2014/68/EU.

    Paz PMIN

    Minimum pressure switch. For retrofitting to Transfero TI.
    Fitting on site into TecBox and connection to control module.
    TÜV-tested in accordance with VdTÜV Druck 100/1 for specialised equipment and according to PED 2014/68/EU.

    Type
    VN
    [l]
    B
    H
    T
    m
    [kg]
    S
    dpu
    [bar]
    EAN
    Article No
    PMIN 0-6
    16
    82
    180
    40
    0,5
    G1/2
    0-6
    7640148638821
    825 1521
    PMIN 6-16
    30
    82
    194
    30
    0,5
    G1/2
    6-16
    7640148638845
    825 1523

    T = Depth of the device

    Minimum pressure switch. Factory fitted to Transfero TI.Pre connected to control module.TÜV-tested in accordance with VdTÜV Druck 100/1 for specialised equipment and according to PED 2014/68/EU.

    Paz PMIN TI

    Minimum pressure switch. Factory fitted to Transfero TI.
    Pre connected to control module.
    TÜV-tested in accordance with VdTÜV Druck 100/1 for specialised equipment and according to PED 2014/68/EU.

    Type
    VN
    [l]
    B
    H
    T
    m
    [kg]
    S
    dpu
    [bar]
    EAN
    Article No
    PMIN 0-6 TI
    16
    82
    180
    40
    0,5
    G1/2
    0-6
    7640148638814
    825 1520
    PMIN 6-16 TI
    30
    82
    194
    30
    0,5
    G1/2
    6-16
    7640148638838
    825 1522
    PMIN 0-25 TI
    30
    133
    208
    61
    0,5
    G1/2
    0-25
    7640148638852
    825 1524

    T = Depth of the device

    7133100

    Select a format Download

    Transfero_TI_Connect_front

    Select a format Download

    Transfero_TI_techbox

    Select a format Download

    7133300